Table 8.9 honeywell pid parameters – Flowserve 3400IQ Digital Positioner User Manual

Page 60

Advertising
background image

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

0

Table 8.9 Honeywell PID Parameters

Parameter Name

Description/Parameter Contents

ERROR_ABS

Absolute value of the difference between PV and working set-point. (Read-
only parameter.)

WSP

Working set-point. This is the set-point value after absolute and rate limits
have been applied. Deviation alarms are computed on this value. (Read-
only parameter.)

BLOCK_TEST

An internal Honeywell test parameter.

PID Block Diagram
Figure 8.4 is a block diagram showing the key components of the PID control function block.

Figure 8.4 PID Control Block

PID Block Description
PID control function block is an algorithm that produces an output signal in response to the
measured variable and the set-point. The PID function block allows the user to choose either a
standard PID control equation (Ideal) or a robust PID equation defined by Honeywell. This selection is
defined in the PID_FORM parameter.

The output has three terms: Proportional, Integral and Derivative. The output is adjusted by tuning
constants. Three tuning constants are contained in the ideal PID equation.

The robust PID uses four tuning constants.

1. GAIN is the tuning constant of the Proportional term.

2. RESET is the tuning constant of the Integral term.

Setpoint

SP_RATE_DN

SP_RATE_UP
SP HI LIM

SP_LO_LM

SHED_OPT

Mode Select

BKCAL_OUT

GAIN

RESET

RATE

BAL_TIME

PID Control

CAS_IN

RCAS_IN

IN

RCAS_OUT

BKCAL_IN

Output

OUT_ HI_LIM

OUT_LO_ LIM

BAL_T IME

OUT

TRK_SCALE

Output Track

TRK_IN_D

TRK_VAL

SP

PV_FTIME

PV Filter

PV

BYPASS

Bypass

HI/LO

DEV

Alarm

FF_SCALE
FF_GAIN

Feed Forward

ROUT_IN

ROUT_OUT

WSP

Backward

Path Outputs

Target &

Permitted

Mode

Actual &

Normal

Mode

FF_VAL

PID_FORM

ALGO_TYPE

OUT_LAG

GAIN_NLIN

GAIN_COMP

ERROR_ABS

BKCAL_HYS

Advertising