8 block parameter summary – Flowserve 3400IQ Digital Positioner User Manual

Page 62

Advertising
background image

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

2

Table 8.10 PID Tuning Parameter Values

Parameter

Initial
Value

Minimum

Value

Maximum

Value

Comment

PV_FTIME

0

0

200

Units: seconds.

GAIN

0

.004

250

GAIN_NLIN

0

.004

250

RATE (sec.)

0

32 • Ts

7500

The value of ZERO is permitted to turn off rate action.

RESET (sec.)

+INF

2 • Ts

7500

The value of +INF is permitted to turn off reset action.

(Some versions of NI-FBUS Configurator program

cannot set +/- INF)

OUT_LAG

Ideal PID

N/A

N/A

N/A

Fixed for ideal PID form - cannot be configured.

Robust PID

0

2• Ts

7500

Zero permitted, which implies no output lag.

BAL_TIME

0

N/A

N/A

Not used in Honeywell Implementation.

Mode-restricted Writes to PID Parameters
Writing to certain PID block parameters are restricted by the block’s TARGET and/or ACTUAL mode.
The MODE_BLK.TARGET or MODE_BLK.ACTUAL parameter must equal one of the modes in the
‘Write Restrictions Column’ in Table 8.8 before the user can write values to the parameters listed.

Note: Do not select anything in CONTROL_OPTS in order to set the PID action to reverse acting.

8.8 Block Parameter Summary

Table Description
Table 8.11 provides a description of the block parameter attributes that are listed in the Block
Parameter Summary, Table 8.14 to Table 8.17.

Table 8.11 Table Description for Block Parameter Summary

Column Title Attribute

Meaning

Obj Type Object Type

Object type for the parameter value:
S - Simple Variable
R - Record
A - Array of simple variables

Data Type/Structure

Data Type or Structure for the parameter value:
1. Data Types consist of a simple variable or array

and are: Unsigned8, Unsigned16 Unsigned32 - An

unsigned variable of 8, 16 or 32 bits.
Float - Floating point variable.
2. Data Structures consist of a record which may

be: Value and Status - float - Value and status of a

floating point parameter.
Scaling - Static data used to scale floating point

values for display purposes.

Advertising