Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

flowserve.com

PRESS_FLAGS: Each bit within this variable is a flag indicating parameters relevant to the pressure
sensors (Advanced model ONLY). A logic 1 indicates error is active.

Bit

Description

0

0 = No error
1 = Loss of supply

1

Not used

2

0 = No error
1 = Output port 1 sensor failure (low pressure reading during calibration)

3

0 = No error
1 = Output port 2 sensor failure (low pressure reading during calibration)

4

Not used

5

Not used

6

Not used

7

Not used

PRESS_UNITS: This is an enumerated byte that indicates the engineering units being utilized for
pressure sensor reporting. The embedded code supports units of psig, barg, KPag, and Kg/cm2g.
The unit codes are defined as follows:

6 = psi

7 = bar

10 = Kg/cm2

12 = Kpa

SIG_FLAGS: Byte which will be added to the end of each signature data frame to show progress and
end-of-signature. One flag will set STEP or RAMP STATUS_flags

STATUS_FLAG: Status flag variable for fieldbus. When a bit is set, the corresponding flag variable is
reporting an alarm condition.

Bit

Description

0

0 = No error

1 = Error reported in CALIBRATE flags

1

0 = No error

1 = Error reported in TRAVEL flags

2

0 = No error

1 = Error reported in INTERNAL flags

3

0 = No error

1 = Error reported in PRESSURE flags

4

0 = No error

1 = Communications error

5

Not used

6

Not used

7

Not used

TEMP_UNITS: This is an enumerated byte that indicates the engineering units being utilized for
temperature reporting. The embedded code supports °C and ° F. The unit codes are defined as
follows:

32 = °C

33 = °F