TEST_MODE: This variable is bit mapped variable that will allow special tests to be done to the
positioner.

Bit

Test

0

DAC control given to PC, write to DAC_value

1

Blink red LED, used for electronics board test. Bits 2 &

3 may not be set when active

2

Blink yellow LED, used for electronics board test. Bits

1 & 3 may not be set when active

3

Blink green LED, used for electronics board test. Bits

1 & 2 may not be set when active

4

Reserved

5

Reserved

6

Reserved

7

Enable diagnostic scan list

TRAVEL_FLAGS: Each bit within this variable is a flag indicating errors or alerts related to valve
travel. Logic one indicates the flag is active.

Bit

Description

0

0 = No alert

1 = Final_Value_Cutoff active (this can be either high or low)

1

0 = No alert

1 = Lower soft stop active

2

0 = No alert

1 = Upper soft stop active

3

0 = No alert

1 = Lower position alert

4

0 = No alert

1 = upper position alert

5

0 = No alert

1 = Cycle counter limit exceeded

6

0 = No alert

1 = Travel accumulator limit exceeded

7

0 = No alert

1 = Position deviation alert

TRAVEL_UNITS: This is an enumerated byte that indicates the engineering units being utilized for the
travel accumulator and stroke. The unit codes are defined as follows:

47 = inches

49 = millimeters