Limitorque Actuation Systems Modutronic 20 II FCD LMENIM4002-00 – 08/06

24

Symptom

Possible Cause

Corrective Action

Units run in one

direction only

1. Shorted output

1a. Verify proper MANUAL direction operation.

Using ammeter, verify proper command signal,

verify all calibrations have been completed

properly. If you still have difficulty calibrating

the Mod 20 II after verifying the above settings,

replace the Mod 20 II.

No LOCK-IN-LAST

POSITION

1. Missing JP1 Jumper

1a. Locate JP1 Jumper on the Mod 20 II board

and verify connections.

Unit will not follow

signal

1. Bad Potentiometer or

Potentiometer is not centered

1a. Check Pot as discussed in item #7. If Pot

is OK, place the actuator at 50% and check the

resistance between terminals 7-1 and 7-2 or 7-2

and 7-3 with an ohmmeter. See “Adjusting the

Actuator Feedback Potentiometer” (Section 4.3).

Input signal does

not result in full

travel of the valve

1. Mod 20 II not calibrated

correctly

1a. See Section 6 to review the calibration

procedure for the Mod 20 II.

2. ZERO and SPAN adjustments

incorrect

2a. Recalibrate according to procedure in Section

6.

Large input signal

variations result in

little or no actuator

movement

1. Improper analog Input Signal

value

1a. Check for proper Input Signal value.

2. Limit Switch

2a. Check for proper setting. (See appropriate

actuator manual for setting the Limit Switches.)

3. DEADBAND adjustment

3a. Check the DIP Switch accuracy adjustments

shown in Table 6.1.

4. ZERO and SPAN adjustments

4a. Recalibrate according to procedure in Section

6.