4.2.2 Safety Critical User Wiring

The LimiGard concept can be extended to user wiring as shown in Safety Block Diagram - Enhanced User Wiring
(Figure 4.2 below) and configuring the actuator in accordance with subsection 10.5, Custom Input Mode - Momentary
ESD/PSESD (Optional).

NOTE: With enhanced PST/ESD configuration, a momentary ESD demand signal will be honored by the actuator, even if
user wiring is subsequently destroyed during the emergency event.

Figure 4.2 - Safety Block Diagram - Enhanced User Wiring

Case A‐B‐C‐D Meaning Action

Monitor Relay
De‐energises?

1

0001

Invalid STOP

Yes

2

0010

CLOSE

No

3

0011

Invalid STOP

Yes

4

0100

CLOSE

No

5

0101

Invalid STOP

Yes

6

0110

Invalid STOP

Yes

7

0111

STOP

No

8

1000

Invalid STOP

Yes

9

1001

OPEN

No

10

1010

Invalid STOP

Yes

11

1011

Invalid STOP

Yes

12

1100

OPEN

No

13

1101

Invalid STOP

Yes

14

1110

Invalid STOP

Yes

15

1111

Invalid STOP

Yes

Case A‐B‐C‐D Meaning Action

Monitor Relay
De‐energises?

1

0001

Invalid STOP

Yes

2

0010

LOCAL

Yes

3

0011

Invalid STOP

Yes

4

0100

LOCAL

Yes

5

0101

Invalid STOP

Yes

6

0110

Invalid STOP

Yes

7

0111

STOP

Yes

8

1000

Invalid STOP

Yes

9

1001 REMOTE

No

10

1010

Invalid STOP

Yes

11

1011

Invalid STOP

Yes

12

1100 REMOTE

No

13

1101

Invalid STOP

Yes

14

1110

Invalid STOP

Yes

15

1111

Invalid STOP

Yes