3 configurable esd overrides, 4 remote external interlocks/inhibits – Flowserve MX Electronic Actuator SIL Safety IOM User Manual

Page 30

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2350-01 – 9/13

30

FLOWSERVE PROPRIETARY INFORMATION

Use or disclosure of this information is subject to the restrictions on the title page of this document

10.3 Configurable ESD Overrides

The ESD action may also be configured to override the following:
• Inhibit signals.
• Local and Stop position of the Local-Stop-Remote selector switch.
• Over-torque or valve jammed protection.
• Lost phase protection.
• Motor thermal protection.

c

WARNING: Disabling the motor over-temperature, valve jammed or over-torque protection features are permitted,

but by doing so, the user chooses to void the Flowserve warranty and all third-party certifications, including Factory
Mutual, CSA, IECex and ATEX.

10.4 Remote External Interlocks/Inhibits

Three user-defined inputs are provided for the connection of remote contacts that may be used to prevent motorized
operation of the actuator.

These are effective in both remote and local modes and may be overridden by an ESD signal, if so configured.

10.5 Custom Input Mode – Momentary ESD/PSESD (Optional)

The following menus will appear if the customer has the custom mode input option and has enabled custom mode 1 (in
remote control menu).

For custom mode input option and has enabled custom mode 1:

Figure 10.1 - Change Inputs

Following are the preconfigured settings for each input.

Input 0: off, user input, signal present

Input 1: off, PS/ESD enable, signal present

Input 3: on, momentary ESD release, signal present

Input 4, on, momentary ESD release, signal present

Input 5: on, momentary ESD/PSESD, signal present, ESD action close, PS move to target 0%

 

see Note 4

see Note 5

see Note 6

Note 4: The “ESD ACTION” menu will only appear if the status function for the input is “MOMENTARY ESD/PSESD”.

Otherwise the “SIGNAL PRESENT” menu will return to the “CHANGE INPUTS” menu.

Note 5: The “ESD MOVE TO” menu only appears if position is chosen as action .

Note 6: “PS MOVE TO” menu only appears if the status function of the input is “MOMENTARY ESD/PSESD”.

The user will only be able to change the ESD ACTION (and ESD MOVE TO target if ESD action is position, and the PS MOVE TO settings when in this special custom mode 1.

Following are the preconfigured settings for each input.

CHANGE

INPUTS

CHANGE STATUS

INPUT (0)?

STATUS

(OFF)?

INPUT (1)

INPUT (2)

INPUT (3)

INPUT (4)

INPUT (5)

(PSESD ENABLE)

(MOMENTARY ESD RELEASE)

(MOMENTARY ESD/PSESD)

(CLOSE)

(OPEN)

(STOP)

(POSITION)

(ABSENT)

(ON)

STATUS FUNCTION

USER INPUT?

ESD ACTION

(IGNORE)-OK?

PS MOVE TO

O% OPEN

ESD MOVE TO

XXX% OPEN

SIGNAL

(PRESENT)-OK?

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

INPUT 0: ON, ESD Time Delay Relay, signal present, ESD action closed.
INPUT 1: ON, User Input, signal present
INPUT 2: ON, User Input, signal present
INPUT 3: ON, Stop
INPUT 4: ON, Open
INPUT 5: ON, Close

The following menus will appear if the customer has the custom mode input option, and has enabled custom mode 1 (in remote control menu). Custom mode 2 is same as mode 1 except there is no

PS sequence available. See Table 4.1.

CHANGE

INPUTS?

CHANGE

INPUT 0?

STATUS

(ON) - OK?

INPUT (1)

INPUT (2)

(CLOSE INHIBIT)

(OPEN INHIBIT)

(BOTH INHIBIT)

(USER INHIBIT)

-

See Note 1

(OFF)

STATUS FUNCTION

ESD - OK?

Note 1: ESD is hard oded for INPUT 0. You can only configure INPUTS 1 and 2 for the other options.

Note 2: TDR DELAY will only show for INPUT 0. All other inputs this is skipped.

Note 3: ESD ACTION menu will only appear if the STATUS FUNCTION for inputs is ESD otherwise

the SIGNAL PRESET menu will return to the CHANGE INPUTS menu.

Note 4: The ESD MOVE TO menu only appears if position is chosen as action.

YES

NO

NO

YES

NO

YES

NO

YES

INPUT 0: ON, ESD Time Delay Relay, signal present, ESD action closed.
INPUT 1: ON, User Input, signal present
INPUT 2: ON, User Input, signal present
INPUT 3: ON, Stop
INPUT 4: ON, Open
INPUT 5: ON, Close

0-1800 SECS

30 SEC INCREMENTS

TDR DELAY

0 SECS - OK?

YES

NO

See Note 2

See Note 3

See Note 4

ABSENT

(IGNORE)

(POSITION)

(STOP)

(OPEN)

SIGNAL

(PRESENT)-OK?

ESD ACTION

(CLOSE)-OK?

ESD MOVE TO

XXX% OPEN

YES

NO

YES

NO

YES

NO

The following menus will appear if the customer has the custom mode input option, and has enabled custom mode 3 (in remote control menu).