2 local command override, 3 stop override, 4 jammed valve override – Flowserve MX Electronic Actuator SIL Safety IOM User Manual

Page 32: 5 lost phase override, 6 over-torque override, 7 motor thermostat override

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2350-01 – 9/13

32

FLOWSERVE PROPRIETARY INFORMATION

Use or disclosure of this information is subject to the restrictions on the title page of this document

11.1.2 Local Command Override

Default = LOCAL>ESD

Select “NO” to choose:

“ESD>LOCAL” – ESD overrides local command to operate actuator

“LOCAL>ESD” – Local command to operate actuator overrides ESD

11.1.3 Stop Override

Default = STOP>ESD

Select “NO” to choose:

“ESD>STOP” – ESD overrides stop command

“STOP>ESD” – Stop command overrides ESD

11.1.4 Jammed Valve Override

Default = JAMMED VALVE>ESD

Select “NO” to choose:

“ESD>JAMMED VALVE” – ESD overrides jammed valve indication

“JAMMED VALVE>ESD” – Jammed valve indication overrides ESD (default)

11.1.5 Lost Phase Override

Default = LOST PHASE>ESD

Select “NO” to choose:

“ESD>LOST PHASE” – ESD overrides lost phase indication

“LOST PHASE>ESD” – Lost phase indication overrides ESD

11.1.6 Over-Torque Override

Default = OVERTORQUE>ESD

Select “NO” to choose:

“ESD>OVERTORQUE” – ESD overrides over-torque situation

“OVERTORQUE>ESD” – Over-torque situation overrides ESD

11.1.7 Motor Thermostat Override

Default = ENABLED

Select “NO” to choose:

“ESD>THERMOSTAT” – ESD overrides Motor Thermostat tripped

“THERMOSTAT>ESD” – Motor Thermostat tripped overrides ESD

NOTE: Disabling the motor thermostat voids all third-party certifications including Factory Mutual, CSA, IECex
and ATEX. Disabling the motor thermostat removes protection from overheating the motor and may cause unsafe
conditions.