7.3.3 Digital Output (Relay Contact) Configuration Options for PST

Status (S) alarm contacts configuration options include the following.

7.3.3.1 PST Active

This function shall be set when PST STATUS is active. This function shall be reset when PST STATUS is configured,
passed or failed.

7.3.3.2 PST Passed

This function shall be set when PST STATUS is passed. This function shall be reset with next PST move command.

7.3.3.3 PST Failed Target

This function shall be set when actuator failed to reach the PST target position. This function shall be reset with the next
PST move command.

7.3.3.4 PST Failed Return

This function shall be set when actuator reached PST target position but failed to return to the initial start position. This
function shall be reset with next PST move command.

7.3.4 PST Status Indicators

Table 7.1 - PST Status Indicators

PST Status

LCD Message

Not configured for PST
Input 1 configured as PST

STATUS OK

Active (test underway, result undefined)

PS ACTIVE

Failed to reach target after PST timer timeout

FAULT INDICATION (if any)

Failed to return to starting position after PST timer timeout

FAULT INDICATION (if any)

Passed

STATUS OK

7.3.5 Recognition of Valid PST Signals

A PST signal on INPUT 1 (Terminal 34) shall be interpreted as a valid PST command signal only when Input 1 is config-
ured as PST and PST is not currently active, and the current position is more than 2% away from the target position.

7.3.6 Rejection of PST Signal

A PST signal on INPUT 1 (Terminal 34, or D2) shall be interpreted as an invalid PST command signal, and actuator shall
not respond to such PST command signal when PST is active or if a fault exists that would prevent actuator movement
(see Section 3.1).

7.3.7 Actions on Recognition of Valid PST Signal

When valid PST command signal received on INPUT 1 (Terminal 34)

• PST status shall be set to Active.
• LCD indicates “PST ACTIVE.”
• Actuator shall move toward PST target position.
• When the actuator reaches target position ± 2%, actuator shall stop, wait for 5 to 10 seconds, and then return to its

starting position ±2%.

• Any status relay configured to change state on active PST shall assume its configured state.