4 proof test period (tpt), 5 failures in time (fit), 6 mean time to restoration (mttr) – Flowserve MX Electronic Actuator SIL Safety IOM User Manual

Page 8: 7 sff, 8 pfd, 9 rrf, 10 sil vs pfd, Vs rff

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2350-01 – 9/13

8

FLOWSERVE PROPRIETARY INFORMATION

Use or disclosure of this information is subject to the restrictions on the title page of this document

2.4 Proof Test Period (Tpt)

Full stroke test at least once per year ==> 8760 hr

Based upon the extent of the proof test, failures undetected during normal operation or during PST may be uncovered
during full proof test.

2.5 Failures in Time (FIT)

Number of failures in time.

2.6 Mean Time to Restoration (MTTR)

Average failure detection time plus average repair time.

2.7 SFF

Safe failure fraction.

2.8 PFD

avg

The average probability of failure on demand for a safety function (approximate).

2.9 RRF

Risk reduction factor.

2.10 SIL vs PFD

avg

vs RFF

Table 1 is based upon “low-demand Mode,” i.e., the safety function is required to be operated no more frequently than
twice the proof test period (see 2.4 ).

Table 2.1 - SIL vs PFD

avg

SIL

PFDavg

RFF

4

10

-5

… < 10

-4

10,000 to 100,000

3

10

-4

… < 10

-3

1,000 to 10,000

2

10

-3

… < 10

-2

100 to 1000

1

10

-2

… < 10

-1

10 to 100

Advertising