Esd (emergency shutdown) overrides, 1 esd override setup procedure, 1 inhibit override – Flowserve MX Electronic Actuator SIL Safety IOM User Manual

Page 31

Advertising
background image

31

Limitorque MX Electronic Actuator FCD LMENIM2350-01 – 9/13

flowserve.com

FLOWSERVE PROPRIETARY INFORMATION

Use or disclosure of this information is subject to the restrictions on the title page of this document

11

An external contact may be used to place the actuator in emergency shutdown mode. An ESD contact may be connected
to the actuator to override existing command signals and send the valve to a predetermined position.

11.1 ESD Override Setup Procedure

It may be desirable that ESD override other events. These events are selectable. The “>” symbol after ESD indicates that
ESD will override that particular event; inputs through motor thermostat list the choices.

Figure 11.1 - Configuring SIF (ESD) priority

11.1.1 Inhibit Override

Default = INHIBIT>ESD

Select “NO” to choose:

“ESD>INHIBIT” – ESD overrides active • inhibit signal

“INHIBIT>ESD” – Active inhibit signal will override ESD

NOTE: Removing the wires to these terminals can disable active inhibit.

YES

YES

YES

NO

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

*

*

*

* CAUTION: The user may select “ESD” to

override these situations. Should these

conditions occur and the user has

selected “ESD>,” be advised that

the actuator motor may be compromised

Therefore, selection of “ESD>

in these situations will void the

warranty and certification.

*

CHANGE

ESD OVERRIDES?

PRIORITY

INHIBIT>ESD

PRIORITY

LOCAL CMD>ESD

PRIORITY

STOP>ESD

PRIORITY

JAMMED>ESD

PRIORITY

LOST PHASE>ESD

PRIORITY

OVERTORQUE>ESD

PRIORITY

INHIBIT<ESD

PRIORITY

LOCAL CMD<ESD

PRIORITY

STOP<ESD

PRIORITY

ESD>JAMMED

PRIORITY

ESD>LOST PHASE

PRIORITY ESD>

OVERTORQUE

PRIORITY

NW ESD>LOCAL ESD

PRIORITY

*

YES

YES

NO

PRIORITY

THERMOSTAT>ESD

PRIORITY

ESD>THERMOSTAT

*

YES

YES

YES

NO

PRIORITY

2SPD > ESD

PRIORITY

ESD > 2SPD

*

LOCAL ESD>NW ESD

YES

YES

NO

PRIORITY

OIL OVERTEMP>ESD

PRIORITY

ESD>OIL OVERTEMP

*

YES

YES

NO

PRIORITY

TORQUE TIMER>ESD

PRIORITY

ESD>TORQUE TIMER

ESD (Emergency

Shutdown) Overrides

Advertising