6.8 Making Initial Checks

Identifying the Logix 3400 Digital Positioner

Before proceeding, verify the following to make sure that the user is communicating with the correct Logix 3400MD digital positioner:

Device type = 0 x 0203

Device ID = 464C530203-FLS-LX3400MD-00nnnnnnnn

Device tag, (tag description of the Logix 3400MD digital positioner)

Firmware revision level (revision level of the firmware elements)

Table 6.4 Logix 3400MD Digital Positioner Identification

Step

View Parameter

Verify

1

RS.DEV_TYPE

The value is = 0x0203

2

DEVICE_REVISION

DD_REVISION

The values are correct for the DD files provided.

3

Physical Device Tag

NOTE: The device tag name is not contained in a parameter. It can be set and

viewed using the field bus device configurator application.

The physical device tag is correct.

6.9 Configuration Tasks

Device Configuration Procedure Overview

A typical device configuration consists of the following tasks listed in Table 6.5 using the NI-FBUS Configurator application. Details on using
the configurator application are found in the NI-FBUS Configurator user manual supplied with the application software.

This procedure assumes that the hardware installation of the Logix 3400MD digital positioner is complete and the Logix 3400MD digital
positioner is powered up.

Table 6.5 Logix 3400MD Digital Positioner Configuration Task List

Task

Procedure

Result

1

2

Start the fieldbus process application

Start the fieldbus configurator application

Scans the fieldbus network and provides a listing of all active fieldbus devices on the network

or selected link.
Configurator windows are displayed on screen listing the active fieldbus devices.

3

Select a fieldbus device for configuration

4

5

Change the device and block tags, if desired.

Select/add/edit function blocks to create a function block

application process.

NOTE: Configure block objects in the following order:

1. Resource block

2. Transducer block

3. Analog Output block

4. PID block

Any unassigned tags are given a default tag name by the configurator.

Shows a representation of function blocks in the graphical interface window.

6

7
8

Connect (or wire) function blocks to define process loops.

Change block parameters, if necessary.
Configure trends and alarms

Linkages between function block inputs and outputs are created by using wiring tools. Pre-

configured templates can also be used.

Parameters changed for the process requirements.
Trending and alarms configured according to the process requirements.

9

Adjust the block execution schedule.

The function block execution schedule changed according to the process requirements.

Logix 3400MD Digital Positioner LGENIM3405-02 11/13