8 analog output function block, Ao block description, Ao block connections – Flowserve 400MD Logix User Manual

Page 44

Advertising
background image

Index

Origin Name

Store Date Type

Default Value

78

MFG

FRICTION_LOW_PERCENT_YELLOW

NR

Simple

FLOATING_POINT

0

79

MFG

PRESSURE_DIFFERENTIAL

R

Simple

FLOATING_POINT

0

80

MFG

MD_BLOCK_TEST

R

Array

UNSIGNED8

0,0,0,0,0,0,0,0

81

MFG

EXEC_DELAY

SRW

Simple

UNSIGNED16

0

82

MFG

FRICTION_UNITS

RW

Simple

UNSIGNED8

0

83

MFG

TREND_DATA_1

R

Array

INTEGER16

All 0

84

MFG

TREND_DATA_2

R

Array

INTEGER16

All 0

85

MFG

TREND_DATA_3

R

Array

INTEGER16

All 0

86

MFG

TREND_DATA_4

R

Array

INTEGER16

All 0

87

MFG

TREND_DATA_5

R

Array

INTEGER16

All 0

88

MFG

TREND_DATA_6

R

Array

INTEGER16

All 0

89

MFG

TREND_DATA_7

R

Array

INTEGER16

All 0

90

MFG

TREND_DATA_8

R

Array

INTEGER16

All 0

91

MFG

TREND_DATA_9

R

Array

INTEGER16

All 0

8.8 Analog Output Function Block

AO Block Description

The Analog Output function block serves as the external interface for the transducer function block. The value of SP is used to produce the OUT
value which is then sent to the transducer block to specify the valve position. PV reflects the actual valve position reported by the transducer
block.

The AO function block operates on the output value from a control block [such as PID] and performs the following primary functions (most
can be user configured):

Set-point source selection limiting

Units conversion

Fault state action

Position read back

Alarming

Mode control

Output calculation

The database contains the standard AO block database, as defined in the FF FBAP specifications. Flowserve product extensions are specified
in the Logix 3400MD digital positioner parameter dictionary and are described below.

The interface to the AO block contains the following:

Execute function block

Database read access

Alarm acknowledgment

Database write access

AO Block Connections

CAS_IN is the only linkable input parameter and is used with a PID function block for direct cascade connection. RCAS_IN is a contained input
parameter used for remote cascade connection.

OUT and BKCAL_OUT are linkable output parameters. RCAS_OUT is a contained output parameter for remote cascade connection.

Logix 3400MD Digital Positioner LGENIM3405-02 11/13

44