10 digital input function block, 11 input selector function block, Di block description – Flowserve 400MD Logix User Manual

Page 48: Is block description

Advertising
background image

The functionality of these parameters follows the standard Fieldbus definitions as defined in the Foundation Fieldbus specifications.

8.10 Digital Input Function Block

DI Block Description

The DI block takes the manufacturer’s input data, selected by channel number, and makes it available to other function blocks at its output.
This block operates according to the Foundation Fieldbus specifications. Also found in Section 10.19

Table 8.11 DI Function Block Parameter List

Index Origin

Name

Store

Date Type

Default Value

0

STND DISCRETE_INPUT_BLOCK

SRW

Record

BLOCK

0

1

STND ST_REV

SR

Simple

UNSIGNED16

0

2

STND TAG_DESC

SRW

Simple

OCTET_STRING

“ “

3

STND STRATEGY

SRW

Simple

UNSIGNED16

0

4

STND ALERT_KEY

SRW

Simple

UNSIGNED8

0

5

STND MODE_BLK

SRW

Record

MODE

0x01;0x01;0x19;0x10

6

STND BLOCK_ERR

R

Simple

BIT_STRING

0

7

STND PV_D

R

Record

DISC_S

0;0

8

STND OUT_D

NRWO Record

DISC_S

0;0

9

STND SIMULATE_D

RW

Record

SIM_DISC

0;0;0;0;1

10 STND XD_STATE

SRW

Simple

UNSIGNED16

0

11 STND OUT_STATE

SRW

Simple

UNSIGNED16

0

12 STND GRANT_DENY

RW

Record

ACCESS_PERM

0;0

13 STND IO_OPTS|IO_OPTS_DI

SRW

Simple

BIT_STRING

0

14 STND STATUS_OPTS|STATUS_OPTS_DI

SRW

Simple

BIT_STRING

0

15 STND CHANNEL

SRW

Simple

UNSIGNED16

0

16 STND PV_FTIME

SRW

Simple

FLOATING_POINT

0

17 STND FIELD_VAL_D

R

Record

DISC_S

0;0

18 STND UPDATE_EVT

RW

Record

ALARM_EVENT

0;0;0,0;0;0;9;0

19 STND BLOCK_ALM

RW

Record

ALARM_DISC

0;0;0,0;0;0;0;8;0;0

20 STND ALARM_SUM|ALARM_SUM_DI

SRW

Record

ALARM_SUMMARY

0;0;0;0

21 STND ACK_OPTION|ACK_OPTION_DI

SRW

Simple

BIT_STRING

0

22 STND DISC_PRI

SRW

Simple

UNSIGNED8

0

23 STND DISC_LIM

SRW

Simple

UNSIGNED8

0

24 STND DISC_ALM

RW

Record

ALARM_DISC

0;0;0,0;0;0;0;7;0;0

Block

The functionality of these parameters follows the standard Fieldbus definitions as defined in the Foundation Fieldbus specifications.

8.11 Input Selector Function Block

IS Block Description

The signal selector block provides selection of up to four inputs and generates an output based on the configured action. This block normally
receives its inputs from AI blocks. The block performs maximum, minimum, middle, average and ‘first good’ signal selection. With a combi-
nation of parameter configuration options the block can function as a rotary position switch, or a validated priority selection based on the use
of the first good parameter and the disable_n parameter. As a switch the block can receive switching information from either the connected
inputs or from an operator input. The block also supports the concept of a middle selection. Although the normal configuration for this feature
would be with three signals the block should generate an average of the middle two if four signals are configured or the average of two if three
are configured and a bad status is passed to one of the inputs. Logic is provided for handling uncertain and bad signals in conjunction with
configured actions. The intended application of this block is to provide control signal selection in the forward path only, therefore, no back
calculation support is provided. SELECTED is a second output that indicates which input has been selected by the algorithm.

Logix 3400MD Digital Positioner LGENIM3405-02 11/13

48