Device id, tag name and device address, Address assignment objects, Function block scheduling objects – Flowserve 400MD Logix User Manual

Page 68

Advertising
background image

TIME_LAST_RCVD

PRIMARY_AP_TIME_

PUBLISHER

The application clock time contained in the last clock message.

The node address of the primary time publisher for the local link (bus).

265

266

Dynamic

Set by SM (mgr.) during address assignment

TIME_PUBLISHER_ADDR

The node address of the device which sent the last clock message.

267

Dynamic

Unused

268

MACROCYCLE_DURATION

The length of the macro cycle in 1/32 of a millisecond ticks.

269

Set by SM (mgr.) during address assignment

Device ID, Tag Name and Device Address

Each fieldbus device on the network is uniquely identified by:

Device ID that is set by the manufacturer to identify the device.

Device Name (Tag) set by the user to identify operation

Device Address - a unique numerical address on the fieldbus segment. Address may be set automatically by system management.

Address Assignment Objects

Table 8.24 is a description of the address assignment objects with their object directory index and default values.

Table 8.24 SM Address Assignment Objects

Object Description

OD index

Default Value

DEV_ID

The device ID set by the manufacturer.

270

464C530201-VAL-LX1

400-0nnnnnnnn

PD_TAG

The physical device tag to be set using SET_PD_TAG service. 271

All Spaces

OPERATIONAL_

Controls the state of SM of the device upon power-up.

POWERUP

272

TRUE (SM goes opera tional after power up)

Virtual Field Device (VFD) List Objects Two objects identify the VFDs in the device:

Table 8.25 Virtual Field Device (VFD) List Objects

OD Index

VFD_REF

VFD_TAG

273

1

‘MIB’

274

2

‘Resource’

Function Block Scheduling The SMIB contains a schedule, called the function block schedule, that indicates when that device’s function
blocks are to be executed.

System Management schedules the start of each function block relative to the macro cycle of the device. The macro cycle represents one
complete cycle of the function block schedule in a device. The macro cycles of all devices on the link are synchronized so that function block
executions and their corresponding data transfers are synchronized in time.

Using the configurator software, the device’s function block schedule can be pre-configured.

Function Block Scheduling Objects

Four scheduling objects are defined in the Logix 3400MD digital positioner. Table 8.25 lists the func tion block scheduling objects with their
object directory index and default values.

Table 8.25 Function Block Scheduling Objects

Logix 3400MD Digital Positioner LGENIM3405-02 11/13

68