MX-85/140 Maintenance and Spare Parts

61

This serial number is located on the second screen after the “Restricted Settings” screen. It is an eight digit num-

ber after the letters “S/N”. Please refer to the IOM manual, LMAIM1306, supplied with your actuator for the Menu
sequence.

• User must supply this number. Example: 12345678

• Also record the Order Number and Serial Number of the actuator. These numbers can be found on the unit nameplate.

• Once you have acquired the QA Stamp, O/N and S/N, please contact your assigned Service Coordinators for the

keycodes required to turn-on the desired options @ (434) 528-4400.

The “keycode” is then entered into the desired option menu found in “Restricted Settings” using the black knob on

the ACP. A “NO” answer will change the value form 0-9 and A-E. A “YES” answer will truncate to the next space.

After enabling the Modutronic option, please change the remote control wiring scheme to “3-wire maintained.”

For adding the APT, ATT, and AR options, the I/) option board is required. When the I/O board is received and installed

into the actuator, it will already have the option(s) enabled. The unit will recognize the board and turn on the required
software menu feature. Please refer to the IOM manual, LMAIM1306, supplied with your actuator for the Menu
sequence. The user will need to enable the menu options. Please contact your assigned Service Coordinators for
purchase of these desired options @ (434) 528-4400.

For adding the DDC or FF option, the DDC or FF option board is required. When the DDC option board is received and

installed into the actuator, it will recognize the board and turn on the required software menu feature. Please refer to
the IOM manual, LMAIM1306, supplied with your actuator for the Menu sequence. The user will need to enable the
menu options. Please contact your assigned Service Coordinators for purchase of the DDC option @ (434) 528-4400.

5.4 Restoring Power to Actuator with New Control Module

Figure 5.3 – Restoring Power to Actuator with New Control Module

Yes

No

No

Yes

No

No

Yes

Yes

Yes

No

No

Yes

Yes

UNIT SIZE

MX-05-OK?

VOLTAGE

460 VOLT-OK?

Hz

60 Hz-OK?

ACTUATOR RPM

12/18-OK?

S/N

0------OK?

COLD (-50ºC) UNIT

YES/NO -OK?

LOAD DEFAULT

UNIT SETTINGS?

INITIALIZE?

LOAD COLD TEMP

DEFAULTS?

INITIALIZE?

Answer “No” until the

correct unit size is

displayed. Refer to

nameplate.

Answer “No” until

the correct voltage

is displayed. Refer

to nameplate.

Answer “No” until

the correct frequency

is displayed. Refer to

nameplate.

Answer “No” until

the correct RPM

is displayed. Refer

to nameplate.

Answer “No” until the

value is displayed and

then “Yes” to enter.

Refer to namplate for

S/N.

Answer “No” to

select normal

temperature

parameters, -

30ºC to +70ºC.

Answer “Yes” to select arctic

temperature parameters, -

-50ºC to +60°C.

Answer “Yes” to

load default

settings. Unit will

now have factory

default settings.

Please refer to Limitorque Accutronix

MX Customer Connection(s) Diagram

(#L2180) reverse side (located on the

inside of the terminal compartment

cover) for customer default

configuration.

Answer “No”

to change.

Answer “Yes”

to save

settings.

Answer “No”

to change.

Answer “Yes”

to load cold

temperature defaults.

Answer “No”

to change.

Answer “Yes”

to save

settings.

No

Yes

No

Yes

No

Yes