Limitorque MX Maintenance and Spare Parts FCD LMENIM2314-00 – 07/08

146

STEP 3

Route the terminal block plug bundle over the top of the reverser assembly and mount the terminal
block per Section 5.8.2, Steps 7 through 10.

STEP 4

Mount the solid state reverser assembly (1-52) in the unit housing using the existing M4 contactor
mounting screws (8-28).

Figure 5.24 – Control module reinstallation

1-53

1-19

1-57

FUSE

BLOCK PLUG

1-45

1-55

1-56

1-54

STEP 5

Mount the washer (1-56) and the third standoff (1-55) in the housing.

STEP 6

Mount the motor per Section 4.1.2.

STEP 7

Mount the Main/LCS, and if applicable, an optional board into CP using M4 Screws (7-44) per
Section 5.2.2.

NOTE: Only one optional board may be used with the SSMR, either I/O or Network (but not both) in
the same actuator.

STEP 8

Mount the SSMR fuse assembly (1-53) using two pan head machine screws (1-57). See Figure 5.23.