4.2 Usage of System Output Signals in the Compatible Mode

The usage of each system output signal in the compatible mode is described
below.

4.2.1 Robot Power ON Complete

(1) Function

The signal outputs to the external device that OPERATION
PREPARATION START is possible.

(2) Terminal number

No.9 of connector CN10.

(3) Usage

OPERATION PREPARATION START will be executed after this signal and
the auto mode signal are turned ON after the power was turned ON.

(4) ON conditions

 The signal will be turned ON when the Robot Controller system

program properly starts. Preparations for operation can be started after
the power was turned ON.

‚ The signal will be turned ON when the robot failure is cleared by the

OK or Cancel key of the operating panel or the teach pendant or by
CLEAR ROBOT FAILURE and OPERATION PREPARATION START
signals, after the power was turned OFF.

(5) OFF conditions

The signal will be turned OFF when a robot failure or robot warning signal
is turned ON.

Robot Power ON Complete Output

The system properly
starts to operate after
the power is turned
ON.

Robot error

ROBOT POWER ON
COMPLETE output

A robot error is cleared by the OK or Cancel

key of the operating panel or teach

pendant.

When a robot error was cleared with CLEAR

ROBOT FAILURE and OPERATION PRE-
PARATION START signals from the external
device.