Section 3-3-1: venting layout, Installation – Montigo H42DF User Manual

Page 12

Advertising
background image

H*42DF Indoor Gas Fireplace

Page 12

XG0148 - 150204.1

Installation

The Venting Graph: H*42DF*
Measure the vertical height from the fireplace hearth to the centre of the

termination and the horizontal run from the fireplace flue collar to the wall

flange of the termination. Plot on the Venting Graph Figure 13 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 84" and the horizontal run to

the wall flange of the vent termination is 36", this would be an acceptable

installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 72" and the horizontal run to

the wall flange of the vent termination is 66", this would be an acceptable

installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 72" and the

horizontal run to the wall flange of the vent termination is 108", this would

NOT be an acceptable installation.

Figure 13. H*42DF* Top Vent Venting Graph for wall mounted terminations.

Section 3-3-1:

Venting Layout:

Wall mounted termination. Selection of components and details

of venting layout should adhere to the following guidelines:

„

Vent terminations must not be recessed in walls or siding.

„

For Heat Shield requirements see Section 3-3-3.

„

Once the proposed venting layout has been determined refer

to Figure 13 or 15 to ensure the layout is acceptable.

Notes Wall Mounted Terminations: TOP VENT

„

All measurements for vertical or horizontal runs are measured

from center of the vent pipe.

„

Venting runs must fall within the limits set by the venting graph,

see Figure 13.

Wall mounted Terminations

The following details are some possible configurations for Wall

mounted terminations.

Figure 13a. Top Vented, wall mounted installation with one 90° bend. The vent

run must comply with Venting Graph for Top vent, wall mounted terminations,

Figure 13.

Figure 13b. Top Vented, wall mounted Multi-elbow installation. See Venting

Graph for Top vent, wall mounted terminations, Figure 13.

42”

46”

B

C

A

Ve

rtical Run (in.)

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

If your installation does not fall

within the venting graph parameters,

please contact a local Montigo

dealer for Power Venting options.

Solid Section

Flex Section

Hearth

15’foot Max.

Heat

Shield

Termination

Exterior

Wall

Heat

Shield

Termination

Hearth

Exterior

Wall

46”Min.

42” Max.

Flex or Ridig

section