Clearances, Installation – Montigo H42DF User Manual

Page 9

Advertising
background image

H*42DF Indoor Gas Fireplace

Page 9

XG0148 - 150204.1

Installation

Figure 9a. Flue cover and collar installation, Rear Vented fireplace

8” Outer Flue Collar

5” Inner Flue Collar

Flue Gasket

Flue Cover Plate

Clearances

When installing a shelf over the top of the fireplaces, the following

guidelines must be adhered to:

For Rear Vent applications, the minimum clearance is 1" from the rear

of the fireplace to a wall, or any combustible materials, and 9" clearance

from the top of the fireplace to the underside of any combustible shelf

materials.

For Top Vent applications, the minimum clearance is 1" from the rear

of the fireplace to a wall, or any combustible materials, and 17 1/2" to

the underside of any combustible shelf materials, Figure 4.

1” clearance is maintained on sides and bottom of vent runs and 2”

above horizontal vent runs to any combustible material.

The fireplace clearances:

H*42DF

9" 17 1/2" 1" 1" 0

See Section 6

Finishing around

the fireplace

MODEL

Top - Rear V

ent

Top - T

op V

ent

Back

Sides

Floor

Mantel

6”

Figure 7. Installing the Nailing Flange Extension.

Installing The Standoffs
To avoid elevated mantel temperatures, all H*42DF* gas

fireplaces are required to have the supplied standoffs installed.

The fireplace is supplied with two standoffs. Bend and install these

standoffs on top of the fireplace ensuring that the height of the standoff

maintains a 6" clearance.

Figure 6. Installing the standoff's.

Installing the Nailing Flange Extension

Once the fireplace is placed into the rough framed opening, the supplied

Nailing Flange (Part No. H42074) must be fasten securely into place,

with nails or wood screws. as shown in Figure 7.

Note: The nailing flange extension can be substituted with a piece of

NON-Combustible material of the same size and thermal characteristics,

ie: cement board or equivalent. This is recommended in applications

where the facing materials will not adhere to the metal nailing flange.

6"

Note: Clearance from top of fireplace to a ceiling within the fireplace

enclosure.