LDVPV47 Linear Power Vent System

XG0181 - 112811

Appendix

Appendix A: Termination Locations

A = clearance to the termination frame above grade, veranda, porch, deck, or

balcony [16 inches (41 cm) minimum]
B = clearance to door, or sides and top of window, that may be opened [16

inches (41 cm) minimum for appliances ≤100 000 BTU/H (30kW)]
C = clearance to bottom of window that may be opened horizontally [36 inches

(92 cm) minimum for appliances ≤100 000 BTU/H (30kW)]
D = no clearance to permanently closed window when installed with approved

glass penetration termination
E = clearance to permanently closed window [16 inches 41 cm recommended

to prevent condensation on window]
F = vertical clearance to ventilated soffit located above the termination within

a horizontal distance of 2 feet (61 cm) from the centreline of the termination [22

inches (56 cm) minimum]
G = clearance to unventilated soffit [16 inches (41 cm) minimum to non-

combustibles] [22 inches (56 cm) minimum to combustibles]
H = clearance to outside corner [9 inches (23 cm) minimum]
I = clearance to inside corner [12 inches (31 cm) minimum]
J = * not to be installed above a meter/regulator assembly within

40" (103 cm) horizontally from the centreline of the regulator
K = clearance to service regulator vent outlet [3 feet minimum in the United

States] [*6 feet (1.8 m) minimum in Canada]
L = clearance to non-mechanical air supply inlet to building or the combustion

air inlet to any other appliance [16 inches (41 cm) minimum for appliances ≤100

000 BTU/H (30kW)]
M = clearance to mechanical air supply inlet [*6 feet (1.8 m) minimum]
N = † clearance above paved sidewalk or a paved driveway located on public

property [*7 feet (2.1 m) minimum]
P = clearance under veranda, porch, deck, or balcony [16 inches (41 cm)

minimum‡ to non-combustibles] [22 inches (56 cm) minimum‡ to combustibles]
Q = clearance above a roof [24 inches (61 cm) minimum]
R = clearance to adjacent walls and neighboring buildings [18 inches (46 cm)

minimum]
S = clearance from corner in recessed location [12 inches (31 cm) minimum]
T = maximum depth in recessed location [48 inches (122 cm) minimum]
U = minimum width for back wall of recessed location [24 inches (61 cm)

minimum]
V = no horizontal clearance between the frames of two terminations that are

level.
W = horizontal clearance between the frames of two terminations that are not

level. [36 inches (92 cm) minimum]
† a vent shall not terminate directly above a sidewalk or paved driveway

which is located between two single family dwellings and serves both dwellings
‡ only permitted if veranda, porch, deck, or balcony has an open side that

is equal to or greater than the depth of the enclosed area
* as specified in CGA B149 Installation Codes. Note: local Codes or

Regulations may require different clearance.