MD44-DV Direct Vent Vented Fireplace

Installation

PEL-90 Elbow

PTKO Termination

Figure 10.

Extended installation using PIHR-10.

Hearth

Flex Section

Solid Section w/
90° Elbow

Termination

Exterior
Wall

126"

150" max.

Figure 11.

Retracted installation using PIHR-10.

Hearth

Flex Section

Termination

Exterior
Wall

126"

30" Max.

Solid Section w/
90° Elbow

NOTES:

All dimension lengths for vertical or horizontal runs are

measured from center of the 7" elbow.

Venting runs

must fall within the limits set by the venting

graph (see Figure 7).

Flex sections with no vertical rise must not exceed
maximum horizontal length of 3 feet

(see Figure 12).

Flex runs over 3 feet must fall within the limits set by
the venting graph, and must have a minimum vertical
rise of 3" per foot of flex.

Figure 8.

Simple Top Vent installation. If the 90° elbow is installed
directly on the fireplace, the height to the center of the
termination is 49 5/8".

PEXT Section

PEL-90

Elbow

Termination

Figure 9.

Typical Top Vent installation. The solid sections can be
used in various combinations to obtain the desired vent
run. The vent run
must fall within the limits set by the
venting graph.

Horizontal Venting

Hearth

Termination

Exterior
Wall

3' max.

Flex Section

Figure 12 .

Horizontal flex installation with no vertical rise.

Top Vent