Installation, Installation of vertical vent dv – Montigo MD44 DV User Manual

Page 8

Advertising
background image

Part No. XG0120

Page 8

MD44-DV Direct Vent Vented Fireplace

Installation

Installation Of Vertical Vent DV

n

Vertical Terminations must be installed:

minimum 2' (two feet) above the highest point where
vent passes through the roof.

minimum 6' (six feet) from a mechanical air inlet

minimum 18" (1 1/2 feet) from a parapet wall.

n

Maximum vent height is 30 feet above fireplace.
Note: Flame characteristics will change if the maximum vent height
is used.

n

Minimum clearances 1" from vent to all combustible materials must
be maintained.

n

A maximum of two offsets (each offset has two 90° bends) may be
made and shall not exceed total length of 25% of the vertical vent height,
when measured center to center of piping.

Example:

Typical vent installation.
20' vertical vent
2 - 2' offsets required
25% of 20' = 5' max. offset allowed

This venting configuration meets requirements.

A - Termination

PVTK-1

B - Flex sections

PFL-1 (12" section)

PFL-2 (24" section)

PFL-3 (36" section)

PFL-4 (48" section)

C - Solid sections

PEXT-1 (12" section)

PEXT-2 (24" section)

PEXT-3 (36" section)

PEXT-4 (48" section)

PEXT-6 (72" Section)

D - Support Ring & Plate

PSPXT-8 (8" dia.)

E - Firestop

PS-8 (8" dia.)

F - Roof Flashing

PRF-7 (1/12 - 7/12 pitch)

PRF-12 (7/12 - 12/12 pt.)

PRF-16 (12/12 - 16/12 pt.)

2' min.

Storm collar

Support ring

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Storm collar

Support ring

PEXT
Solid Section

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Firestop

2' min.

PXT-10

Adaptor

PEXT

Flue

Collar

Figure 15.

Vertical venting with 2 offsets (1 offset= two 90° bends).

Figure 14.

Vertical venting with 1 offset (1 offset= two 90° bends).

2' min.

2'

Storm collar

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support straps or
support plate & ring

Firestop

Firestop

Firestop

Support plate
& ring

Figure 13.

Straight, vertical venting using the required PXT-10
adaptor.

Top Vent

Advertising