Niveo Professional NUPS22-6000U User Manual

Page 22

Advertising
background image

1) Bypass setting

Interface

Description

1. Status (only available in bypass / AC mode)

1.1 Open/Forbid:

Open: Bypass allowed. When selected, UPS will run at Bypass

mode depending on bypass enabled/disabled setting.

Forbid: Bypass not allowed. When selected, it’s not allowed for

running in Bypass mode under any situations.

1.2 Enable/Disable

This option appears only when Bypass status is set to “Open”.

Enable: Bypass enabled. When selected, Bypass mode is

activated.

Disable: Bypass disabled. When selected, automatic bypass is

acceptable, but “manual bypass” is not available. “Manual bypass”

means users manually operate UPS to Bypass mode (for example,

in AC mode turning off the UPS to Bypass mode). Then, the UPS

will go to bypass mode but without output if it is turned off in AC
mode.

NOTE: The following items are only available in bypass mode:

2. HighLoss V: Set the acceptable high voltage for bypass. Setting

range is from (Rated Output Volt +11V) to 276V and the default

value is 264V.

3. LowLoss V: Set the acceptable low voltage for bypass. Setting

range is from 110V to (Rated Output Volt - 11V) and the default

value is 110V.

4. HighLoss F: Set the acceptable high frequency for bypass.

50 Hz: Setting range is from 51Hz to 54 Hz.

60 Hz: Setting range is from 61Hz to 64Hz.

The default value is 54.0Hz/64.0Hz.

5. LowLoss F: Set the acceptable high frequency for bypass.

50 Hz system: Setting range is from 46.0Hz to 49.0Hz.

60 Hz system: Setting range is from 56.0Hz to 59.0Hz.

The default value is 46Hz/56Hz.

2) ECO setting (only available or effective on bypass mode)

Interface

Description

1. Status

Enable: Enable ECO Function

Disable: Disable ECO Function

If ECO function is disabled, voltage range and frequency range for

ECO mode still can be set, but it is meaningless unless the ECO

function is enabled.

2. HighLoss V: High voltage point in ECO mode. The setting range

is from +5% to +10% of the nominal voltage.

3. LowLoss V: Low voltage point in ECO mode. The setting range is

from -5% to -10% of the nominal voltage.

4. HighLoss F: Set low frequency point for ECO mode.

50 Hz system: Setting range is from 46Hz to 48Hz.

60 Hz system: Setting range is from 56Hz to 58Hz.

The default value is 48Hz/58Hz.

5. LowLoss F: Set high frequency point for ECO mode.

50 Hz: Setting range is from 52.0Hz to 54.0 Hz.

60 Hz: Setting range is from 62.0Hz to 64.0Hz.

The default value is 52.0Hz/62.0Hz.