Specifications – Niveo Professional NUPS22-6000U User Manual

Page 31

Advertising
background image

6. Specifications

MODEL

6000U

10000U

CAPACITY*

6000 VA / 5400 W

10000 VA / 9000 W

INPUT

Voltage
Range

Low Line Loss

110 VAC ± 3 % at 50% Load;

176 VAC ± 3 % at 100% Load

Low Line Comeback

Low Line Loss Voltage + 10V

High Line Loss

300 VAC ± 3 %

High Line Comeback

High Line Loss Voltage - 10V

Frequency Range

46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system

Phase

Single phase with ground

Power Factor

0.99 at 100% Load

OUTPUT
Output voltage

200V/208/220/230/240VAC

AC Voltage Regulation

± 1%

Frequency Range

(Synchronized Range)

46Hz ~ 54 Hz @ 50Hz system

56Hz ~ 64 Hz @ 60Hz system

Frequency Range (Battery Mode)

50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz

Overload

Line mode

100%~110%: 10min;

110%~130%: 1min;

>130% : 1sec

Battery mode

100%~110%: 30sec;

110%~130%: 10sec;

>130% : 1sec

Current Crest Ratio

3:1 max

Harmonic Distortion

2 % @ 100% Linear Load;

4 % @ 100% Non-linear Load

Transfer

Time

Line

Battery

0 ms

Inverter

Bypass

0 ms

Inverter

ECO

<10 ms

EFFICIENCY
Line mode

> 90%

Battery Mode

> 88%

BATTERY

Standard

Model

Type & Numbers

12 V / 7 Ah x 20

12 V / 9 Ah x 20

Recharge Time

7 hours recover to 90% capacity

9 hours recover to 90% capacity

Charging Current

1 A ± 10% (max.)

Charging Voltage

273 V ± 1%

Long Run
Model

Type

Depending on applications

Numbers**

18 – 20

Charging Current

4 A ± 10% (max.)

Charging Voltage

273 V ± 1%

PHYSICAL

Dimension,DXWXH(mm)

UPS unit: 580X438 X133

Battery pack: 580X438 X133

UPS unit: 668X438 X133

Battery pack: 580X438 X133

Net Weight (kgs)

UPS unit: 20

Battery pack: 57

UPS unit: 23.5

Battery pack: 63

ENVIRONMENT
Operation Temperature

0 ~ 40°C (the battery life will down when > 25°C)

Operation Humidity

<95 % and non-condensing

Operation Altitude***

<1000m

Acoustic Noise Level

Less than 58dB @ 1 Meter

Less than 60dB @ 1 Meter

MANAGEMENT
Smart RS-232 or USB

Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC

Optional SNMP

Power management from SNMP manager and web browser

* If the UPS is in converter mode, the power capacity will be derated to 60% of full capacity;
**If the battery number is 18, the power capacity will be derated to 90%; if it is 19, the power capacity will be derated to 95%;

***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.

Product specifications are subject to change without further notice.

Advertising
This manual is related to the following products: