Product specifications

9

Product specifications

9.1

Technical data

Nortec ME Control

Supply voltage control unit

100...240 VAC/50...60 Hz

Supply voltage circulation pumps

24 Vdc/50...60 Hz

Power consumption

1)

< 278 W (5 stages, no options fitted)

Control signals

0...5 VDC

1...5 VDC

0..10 VDC

2...10 VDC

0...16 VDC

3.2...16 VDC

0..20 mA

4..20 mA

On/Off (via volt-free contact)

Control accuracy

Control accuracy depends on air conditions, control

distance, water quality and on the number of On/Off

cycles

Max. admissible matric face velocity

3.5 m/s (689 fpm)

4.5 m/s (886 fpm) with droplet separator

Water supply

ø15mm (0.625") compression fitting

Water drain (outside diameter)

ø 54 mm (2.125") - Tank /

ø 28 mm (1.125") - Hydraulic module

Admissible water supply pressure

2...5 bar (29...72.5 psi)

Admissible water temperature

5...20 °C (41...68 °F)

Water quality

Tap water, softened or fully demineralised water with a

max. of 100 cfu/ml

Admissible operating air temperature

10...60 °C (50...140 °F)

Admissible ambient temperature (Control unit)

1...40 °C (33.8...104 °F)

Admissible ambient humidity (Control unit)

max. 75 %rh

Degree of protection of Control unit

IP21

Degree of protection of Hydraulic module

IP42

Conformity

CE marking

Fire classification of evaporative media

glass fibre media: A2-S2,-D0 (UL Class 1)

polyester media: DIN EN 53438 Class F1

1)

Power consumption depending on the number of vertical evaporative cassettes banks and the options fitted