3.1.4 Pipe System Requirements

The straight run requirements presented below represent the minimum requirements
for accurate flow measurement. For optimum performance, provide as much additional
straight run as possible.

IMPORTANT NOTE

For proper operation, install the flow meter in a straight run of pipe free of bends, tees, valves,

transitions and obstructions for a distance of at least 3 diameters upstream and 2 diameters

downstream.

i

Recommended Installation

Place pipe at least 3 pipe

diameters downstream and

2 pipe diameters upstream

from bends and obstru-

tions.

Avoid downward flow

which can lead to partially

filled pipes.

The electrodes should

be located in the

horizontal axis (3 o’clock
and 9 o’clock) in order to

prevent sediment from

settling on them.

Avoid these installations

3 DIA

2 DIA

3 DIA

2 DIA

3 DIA

2 DIA

Electrode Location