ONICON F-3200 Series User Manual

Page 8

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-3200 Flow Meter Manual 05/14 - 0671-12 / 18325

Page 8

1.4 STANDARD FEATURES AND SPECIFICATIONS

• A built-in user interface & graphic display

• A single 4 – 20mA output for flow rate

• Two programmable open collector pulse outputs. Outputs may be programmed to provide:

* an indication of flow direction

* a scaled pulse for totalizing flow

* a high resolution frequency output to drive peripheral devices

* an indication of an alarm condition

• Empty pipe detector

• Internal self-diagnostic functions & fault alarms

CALIBRATION

Flow meters are wet calibrated in a flow laboratory

against standards that are directly traceable to

government standards. A certificate of calibration

accompanies every meter.
ACCURACY

Accurate to within:
± 0.2% of reading from 1.6 to 33 ft/s
± 0.0033 ft/s at flows less than 1.6 ft/s

PROGRAMMING

Factory programmed for specific application
MEMORY

Nonvolatile memory retains all program parameters

and totalized values in the event of power loss.
DISPLAY

Alphanumeric LCD displays total flow, flow rate,

flow direction & alarm conditions
OUTPUT SIGNALS

Isolated 4 – 20mA analog output for flow rate

2 isolated programmable opto-coupled open

collector digital/pulse outputs

(Configurable for frequency, pulse, alarm or

directional flow)

40VDC, 100mA and 1250Hz maximum
(Optional) Redundant output option with second

isolated analog output for flow rate and 2 additional

isolated programmable opto-coupled open collector

digital/pulse outputs

(Pulse outputs configurable for frequency, pulse,

alarm or directional flow)

40VDC, 100mA and 1250Hz maximum
TEMPERATURE RANGE

Liquid temperature range:

Polypropylene liner: 32° to 140°F

Ebonite liner: 23° to 175°F

PTFE liner: -4° to 212° F (266° F with remote

electronics without pre-amplifier option)

Ambient temperature range: -4° to 140°F
FLUID CONDUCTIVITY

5 µS/cm minimum

MAINTENANCE

Periodically inspect the power supply cables,

cable glands and the enclosure for signs of

damage. Inspect installation and mounting hardware

for loose connections.

MECHANICAL

Electronics Enclosure:

Standard: Painted Aluminum NEMA 6

(Optional) Remote mount w/o pre-amplifier,

maximum distance from sensor - up to 325 ft @
conductivities

≥ 200µS/cm

Remote mount transmitter with pre-amplifier in

sensor body (maximum distance from sensor

body,

1640ft).

Outer Body Material:

Standard: Carbon Steel, Painted

Optional: 316 Stainless Steel

Flow T

ube (Internal):

304 Stainless Steel

Connection Type:

Standard: ANSI 150 Class Flange

Optional: ANSI 300 Class Flange

Optional:

Wafer

Optional: Threaded Process Connection
ELECTRICAL

This equipment is intended for INSTALLATION

CATEGORY (OVERVOLTAGE CATEGORY) II

applications.
Input Power - Factory Selectable:

Standard - 100 - 240 VAC, 45 - 66 Hz, 12 VA typical

Optional - 18 - 45 VDC, 10 W typical

OR 18 - 45 VAC, 45 - 66 Hz, 12 VA typical
Overcurrent Protective Device Ratings:

Supply mains overcurrent protective devices with

the following ratings:

• 120VAC 50/60 Hz – 15 A

• 230VAC 50 Hz – 6 A
Wiring:

Flow signals - Use 18-22 AWG shielded cable

Standard input power - Use a three wire service

with one wire a protective earth ground. The

installation must comply with all local, state and

federal

building

codes.

Optional input power - Use PVC jacketed copper

cable with a wire gauge suitable for the length of

run and required maximum current carrying

capacity. The installation must comply with all

local, state and federal building codes.

Note: Specifications are subject to change wit

hout notice.