Danger – Pennco 3KW0.60 User Manual

Page 14

Advertising
background image

14

Boilers may be factory packaged with tankless heater

coil see figure below. Coil provides instantaneous heating

of water for domestic use if proper burner and water supply

line controls are used. Tankless coils are meant to provide

domestic hot water for intermittent draws, not continuous

flow.

NOTICE

Do not use tankless coil if your water is excessively

hard with lime or other deposits which will

accumulate inside the coil.

Boiler configured so Honeywell L4006A Low Limit mounts

on control well (provided). Mount factory-wired low limit

control on tankless coil. Tempering valve (mixing valve) is

also recommended as shown in figure below. Flow restrictor

may be required on tankless coil inlet piping so flow rates

are matched to boiler heat input (see table).

DANGER

Water temperatures exceeding 125°F will cause

severe burns instantly or death by scalding.

!

Boiler

Model

Burner

Firing

Rate (gph)

Input

(MBH)

Tank less

Rating

(gpm)‡

3KW0.60C

0.60

84

2.85

3KW0.75C

0.75

105

3.00

3KW1.00C

1.00

140

3.25

4KW.90C

0.90

126

3.15

4KW1.25C

1.25

175

3.50

4KW1.50C

1.50

210

3.75

5KW1.20C

1.20

168

3.45

5KW1.75C

1.75

245

4.00

5KW2.00C

2.00

280

4.25

‡ Gallons of water per minute heated from 40°F to 140°F

with

200°F boiler water temperature, intermittent draw

SYSTEM PIPING

Tankless Coil Piping Arrangement

Figure 10 -Tankless Coil Piping Arrangement