Pennco 3KW0.60 User Manual

Page 9

Advertising
background image

9

B. All Air from Outdoors: Confined space shall

be provided with two permanent openings,

one commencing within 12 inches of top and

another commencing within 12 inches of bottom

of enclosure. Openings shall communicate

directly, or by ducts, with outdoors or spaces

(crawl or attic) that freely communicate with
outdoors.

1.

When directly communicating with outdoors, each

opening shall have minimum free area of one

square inch per 4,000 Btu per hour of total input

rating of all equipment in the enclosure.

2.

When communicating with the outdoors through

vertical ducts, each opening shall have a minimum

free area of one square inch per 4,000 Btu per

hour of total input rating of all equipment in the

enclosure.

3.

When communicating with outdoors through

horizontal ducts, each opening shall have

minimum free area of one square inch per 2,000

Btu per hour of total input rating of all equipment

in the enclosure.

4.

When ducts are used, they shall be of same cross

sectional area as free area of openings to which

they connect. Minimum dimension of rectangular

air ducts shall be not less than three inches.

FRESH AIR DUCT CAPACITIES

THROUGH LOUVERS

Fresh Air

Duct Size

¼” Mesh

Screen

Wood

Louvers

Metal

Louvers

(Btuh)*

(Btuh)*

(Btuh)*

3 ½” x 12”

144,000

36,000

108,000

8” x 8”

256,000

64,000

192,000

8” x 12”

384,000

96,000

288,000

8” x 16”

512,000

128,000 384,000

*Btuh = British Thermal Units per hour based on

opening covered by ¼” mesh screen , wood louvers,

or metal louvers.

FRESH AIR FOR COMBUSTION

Figure 5 - Fresh Air Duct Capacities For Ducts Supplying Fresh Air To Boiler In
Tightly Constructed Houses

Advertising
This manual is related to the following products: