CHIMNEY CONNECTOR AND DRAFT

REGULATOR
Boiler venting requires 6” diameter chimney connector pipe

and use of draft regulator packed with boiler. Regulator

controls draft automatically. Preferred installation is in

horizontal section of pipe, may also install in angled or

vertical section of pipe. Verify “top” of regulator is at top

and short pipe section which holds vane is horizontal.

Install draft regulator as close as practicable to boiler.

ALTERNATE POSITIONS

TOP

TOP

DRAFT REGULATOR

VANE

CRIMPED END

BALANCED WEIGHT

DRAWBAND

LAST PIECE

INSTALLED

MUST SLOPE UP

AT LEAST 1/4 INCH

PER FOOT OF

HORIZONTAL RUN

MUST BE AT LEAST 4

INCHES THICK -

AND BE TIGHT.

TIGHT

CLEAN-OUT

DOOR

SEALED IN

THIMBLE

TIGHT, SMOOTH,

CORRECTLY SIZED.

Minimum Height:

Must be 3 FT higher than

highest part of passage through roof.

Must be at least 2 FT higher than

any neighboring object within 10 FT.

Must have unobstructed top opening

.

TYPICAL CHIMNEY CONNECTION

Chimney connector installation, start at boiler with vertical

pipe and elbow. Install draft regulator making it horizontal.

Slope horizontal pipe up toward chimney at least 1/4 inch

per linear foot of venting. Chimney connector must not leak

and must be firmly supported. Join each section with at

least two sheet metal screws. Support every second section

with stove-pipe wire.

CHIMNEY AND CHIMNEY CONNECTIONS

WARNING

Fire Hazard. Maintain minimum vent pipe clearance of

18” from surface of vent to wood and other combustible

materials. Failure to comply may result in death or

serious injury.

!

Figure 11 -Typical Chimney Connection