Beckett oil burner, nozzle, and air setting – Pennco 3KW0.60 User Manual

Page 31

Advertising
background image

31

NOTE: All burners use insertion depth of 2 ¼” and fired at over-fire draft of 0.02 inches w.c.

Burner settings provided are intended for initial start up only. Final adjustment must be made

using combustion test instruments.

BOILER

MODEL

FIRING

RATE

(GPH)

BURNER

MODEL

HEAD

HEAD

ADJUSTMENT

LOW FIRE

BAFFLE

AIR

BAND

AIR

SHUTTER

STATIC

PLATE NOZZLE**

PUMP

PRESSURE

(PSI)

3KW0.60*

0.60

AFG50MB

L1

FIXED

Yes

0

4

3 3/8”

0.60 x 70W

100

3KW0.75*

0.75

AFG50MB

L1

FIXED

Yes

0

8

3 3/8”

0.75 x 70B

100

3KW1.00

1.00

AFG50MB

L1

FIXED

No

0

10

3 3/8”

1.00 x 70B

100

4KW.90*

0.90

AFG50MD

V1

0

No

0

5

2 3/4”

0.75 x 60B

140

4KW1.25

1.25

AFG50MD

V1

0

No

1

10

2 3/4”

1.25 x 70B

100

4KW1.50*

1.50

AFG50MD

V1

2

No

3

10

2 3/4”

1.50 x 60B

100

5KW1.20*

1.20

AFG50MD

V1

1

No

1

8

2 3/4”

1.20 x 70B

100

5KW1.75*

1.75

AFG50MD

V1

3

No

3

10

2 3/4”

1.75 x 60B

100

5KW2.00

2.00

AFG50MD

V1

4

No

3

10

2 3/4”

2.00 x 60B

100

* “Alternate Firing Rate Kits” are needed in order to achieve these firing rates

** All nozzles are Delavan

BECKETT OIL BURNER, NOZZLE, AND AIR SETTING