Instructions for Limit control provided are included with boiler.

IMPORTANT: Installer follow these instructions carefully.

ADJUST OPERATING CONTROLS: Use following

settings for first adjustment:

High Limit:

Baseboard and Convectors 180°F

Standing Radiators 180°F

Low Limit (when used) 140º ( increase if hotter domestic

water is required, but low limit set point must be at least
20°F less than high limit set point

).

Do not attempt to start burner when excess oil

has accumulated, when unit is full of vapor, or

when combustion chamber is very hot.

Boiler

Model

Dimension “N”

(electrode to

nozzle)

Dimension “H”

(head to nozzle)

All

1/16”

7/32” - 9/32”

Dimension “Z” For L1, V1 Heads

1 ¾”

OPERATING THE BOILER

CHECKING AND ADJUSTING CONTROLS

Figure 13 - Beckett AFG Burner Electrode

Adjustments Variable (V1, L1) Heads

Figure 14 -

Beckett AFG Variable (V1) Head

Adjustments and Settings

When low limit is used:

• With Honeywell L7248L control, set ELL parameter on

L7248L control to ON.

• With Hydrolevel 3250 control, Set Z-l switch on 3250

control to l position.

Boilers factory equipped with tankless coil are factory set.

ADJUST THERMOSTAT HEAT ANTICIPATOR PER

LIMIT INSTRUCTIONS.