Warning – Pennco 3KW0.60 User Manual

Page 8

Advertising
background image

8

Provide enough fresh air to assure proper combustion. Fire

in the boiler uses oxygen. It must have continuous supply.

Air in the house contains only enough oxygen to supply

burner for short time. Outside air must enter house to

replace air used by the burner. Study following examples 1

and 2 to determine your fresh air requirements.

EXAMPLE 1: Boiler Located in Unconfined Space
If your boiler is in open area (non partitioned basement) in

conventional house, air that leaks through cracks around

doors and windows will usually be adequate to provide air

for combustion. Doors should not fit tightly. Do not caulk

cracks around windows.
Unconfined space is defined as space whose volume is not

less than 50 cubic feet per 1,000 Btu per hour of total input

rating of all appliances installed in that space.

EXAMPLE 2: Boiler Located in Confined Space

A. All Air from Inside the Building: Confined space

shall be provided with two permanent openings

communicating directly with additional room(s) of

sufficient volume so that combined volume of all spaces

meets criteria for unconfined space. Total input of all

combustion equipment installed in combined space

shall be considered in making this determination. Each

opening shall have minimum free area of one square

inch per 1,000 Btu per hour of total input rating of all

combustion equipment in confined space, but not less

than 100 square inches. One opening shall be within 12

inches of top and one within 12 inches of bottom of the

enclosure.

Example: Your boiler is rated at 100,000 Btu per hour.

Water heater is rated at 30,000 Btu per hour. Total

is 130,000 Btu per hour. You need two grilles, each

with 130 square inches of FREE opening. Metal grilles

have about 60% FREE opening. To find louvered area

needed, multiply free opening required by 1.7 (130 x

1.7 = 221.0 sq. in. louvered area). In this example,

two grilles each having 8” x 30” (240 sq. in.) louvered

area would be used.

FRESH AIR FOR COMBUSTION

WARNING

Asphyxiation, fire hazard. Do not obstruct air

openings to combustion area. Follow instructions

below, to maintain adequate combustion air.

!

NOTICE

Install outside air intake if you use fireplace or

kitchen or bathroom exhaust fan. These devices rob

boiler and water heater of combustion air.

Figure 4 - Air Openings For Boiler Located In
Confined Space (Utility Room

)

Advertising
This manual is related to the following products: