It is to be ensured that a gate
valve is positioned upstream
and downstream of the dirt
traps. This ensures that the dirt
traps can be checked at any
time without loosing water.

The dirt traps must be checked
during every service of the sys-
tem.

The indoor module contains a
ventilation connection in the
inlet line in order to enable ad-
ditional venting.

It must be ensured that a
suffi cient fl ow-rate is given.

CAUTION

Manual-
deaerator

All visible metallic surfaces must
be additionally insulated.

Cooling mode via the heating
circuit requires a completely
vapour diffusion tight insulation
along the entire length of the
pipework.

All outgoing heating circuits
including the connections for
water heating are to be secured
against circulating water by
means of fl ap valves.

The system must be fl ushed
before commissioning the sys-
tem. The entire system must be
subjected to a tightness check
and a thorough venting.

Electrical connection

For the CMF and CMT devices, a
mains cable must be laid for both
the outdoor and indoor modules.
In some cases it may also be pos-
sible to feed the power supply
for the indoor module from the
outdoor module. The outdoor
modules of Series CMF 80, CMF
90, CMT 100 require a 230V
mains supply. The outdoor mod-
ules of Series CMF 140, CMF 150
and CMT 150 have to be provided
with a 400 V supply. The electrical
connection between the modules
is realised with a 4-wire control
cable.

A clockwise rotating field must
be ensured for 400 V power
supplies.

CAUTION

The following diagram provides an
overview of the required connec-
tions.
The diameters for the leads and
the connection cables are to be
selected according to local regula-
tions.
The fusing level is to be taken from
the technical data.
It is possible that the energy sup-
ply company will provide a special
power supply tariff for the opera-
tion of heat pumps.
Individual tariff options should be
agreed with the local energy sup-
ply company.

Check all plugged and clamped
terminals to verify they are
seated correctly and making a
permanent contact. Re-tighten
as required.

CAUTION

15