Technical data – REMKO CMF-80 v.2 User Manual

Page 43

Advertising
background image

Technical data

Range

CMF 80

CMF 90

CMT 100

CMF 140

CMF 150

CMT 150

confi guration

Heating only

Heating / cool-
ing

Heating / cool-
ing

Heating only

Heating / cool-
ing

Heating / cool-
ing

Inverter technology

REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec

System

Air / water

Air / water

Air / water

Air / water

Air / water

Air / water

Heat pump manager

Multitalent

Multitalent

Multitalent

Multitalent

Multitalent

Multitalent

Storage tank for hydraulic decou-
pling of volumetric fl ows

optional

optional

150 l

optional

optional

150 l

Electric booster heating 6 kW

optional

optional

Series

optional

optional

Series

Water heating

optional

optional

optional

optional

optional

optional

Heating output min / max

kW

3,5 - 10,2

3,5 - 10,2

3,5 - 10,2

5,0 - 16,0

5,0 - 16,0

5,0 - 16,0

Cooling performance min / max kW

3,3 - 8,1

3,3 - 8,1

5,5 - 14,0

5,5 - 14,0

Heating output for A7/W35

kW/COP

1)

8,1 / 4,5

8,1 / 4,5

8,1 / 4,5

14,2 / 4,5

14,2 / 4,5

14,2 / 4,5

Heating output for A2/W35

kW/COP

1)

7,0 / 3,9

7,0 / 3,9

7,0 / 3,9

13,4 / 4,2

13,4 / 4,2

13,4 / 4,2

Heating output for A7/W45

kW/COP

1)

7,3 / 3,2

7,3 / 3,2

7,3 / 3,2

13,1 /3,4

13,1 /3,4

13,1 /3,4

Heating output for A2/W45

kW/COP

1)

6,3 / 2,8

6,3 / 2,8

6,3 / 2,8

12,7 / 3,2

12,7 / 3,2

12,7 / 3,2

Heating output for A7/W55

kW/COP

1)

7,0 / 2,3

7,0 / 2,3

7,0 / 2,3

12,1 / 2,6

12,1 / 2,6

12,1 / 2,6

Heating output for A7/W55

kW/COP

1)

6,0 / 2,1

6,0 / 2,1

6,0 / 2,1

11,6 / 2,4

11,6 / 2,4

11,6 / 2,4

Functional range heating

2)

°C

-20 to +34

-20 to +34

-20 to +34

-20 to +34

-20 to +34

-20 to +34

Functional range cooling

2)

°C

+15 to +46

+15 to +46

+15 to +46

+15 to +46

+15 to +46

+15 to +46

Max. supply temperature heating water

°C

up to +55

up to +55

up to +55

up to +55

up to +55

up to +55

Refrigerant / basic fi lling

-- / kg

R 410A

3)

/ 3,5 R 410A

3)

/ 3,5 R 410A

3)

/ 3,5 R 410A

3)

/ 5.0 R 410A

3)

/ 5,0 R 410A

3)

/ 5,0

Refrigerant, additional quantity

30-50m

g/m

60

60

60

60

60

60

Power supply

V / Hz

230/1~ / 50

230/1~ / 50

230/1~ / 50

400/3~N/50

400/3~N/50

400/3~N/50

Starting current

A

12,5

12,5

12,5

8

8

8

Rated current

A

13

13

13

13

13

13

Rated capacity

kW

3,0

3,0

3,0

9,0

9,0

9,0

Customer's fuse protection (outdoor

unit)Tripping characteristic B

A

25

25

25

3x16

3x16

3x16

Volumetric fl ow water hot water at
∆t 5 K

m³/h

1,4

1,4

1,4

2,2

2,2

2,2

Pressure loss on liquefi er at ∆t 5 K kPa

5,4

5,4

5,4

8,1

8,1

8,1

Pressure loss on indoor module

kPa

11,1

11,1

22,7

22,7

max. airfl ow volume outdoor

module

m³/h

1.900

1.900

1.900

3.530

3.530

3.530

Max. permissible operating pres-

sure hot water

bar

3,0

3,0

3,0

3,0

3,0

3,0

Hydraulic connection supply /

return fl ow

Inches

1“ AG

1“ AG

1“ AG

1“ AG

1“ AG

1“ AG

Noise output LpA 1m (outdoor

unit)

dB(A)

46/38

4)

46/38

4)

46/38

4)

50/42

4)

50/42

4)

50/42

4)

Dimension indoor unit Height /

width / depth

mm

800 / 550 / 550 800 / 550 / 550 1800 / 550 / 550 800 / 550 / 550 800 / 550 / 550 1800 / 550 / 550

Dimension outdoor unit Height /

width / depth

mm

945 / 950 / 330 945 / 950 / 330 945 / 950 / 330 1350 / 950 / 330 1350 / 950 / 330 1350 / 950 / 330

Weight indoor module

kg

52

52

135

55

55

138

Weight outdoor module

kg

75

75

75

130

130

130

1) COP=coeffi cient of performance according to EN 14511
2) Based on the outdoor temperature
3) Contains greenhouse gas according to Kyoto protocol
4) Distance 5 m clear fi eld.

43