LED

s

LEDs on outdoor module

In the event that the red con-
trol lamp lights up on the indoor
module, then the fault is on the
outdoor module. Two LEDs are vis-
ible after removing the enclosure
panel which light up in green and
red during normal operation (see
adjacent fi gure). If the LEDs fl ash,
then there is a fault. Causes and
measures for their remedy can be
taken from the following table.

green LED

red LED

Meaning

Remedial measures

fl ashes 1 time

fl ashes 1 time

Phase error: The supply cable to the out-
door module or the connection between
the indoor and outdoor modules is not
correct.

Check the electrical connection (swapped
phases)Check connection cable

fl ashes 2 time

One of the connectors has been removed
from the PCB or has intermittent contact

Check all connectors on the PCB, check
high and low pressure sensors

fl ashes 3 time

Fault on PCB

Exchange PCB

fl ashes 2 time

fl ashes 1 time

Wiring error between indoor and outdoor
modules

Check connection cable for correct polar-
ity and proper contact

fl ashes 2 time

Data transfer error between indoor and
outdoor modules

Check if the connection cable has been
improperly extended or incorrectly con-
nected

fl ashes 3 time

fl ashes 1 time

Hot gas temperature in refrigerant circuit
too high or hot gas heating too low

Check refrigerant; check hot gas tempera-
ture sensor; check expansion valve

fl ashes 2 time

High pressure valve has tripped

Open any closed spherical valves, check
refrigerant fi lling

Low pressure cut-off switch has tripped

Open any closed spherical valves, check
refrigerant fault

No voltage on condenser

Check power supply to the condenser

fl ashes 3 time

Overheating protection tripped, excessive
liquid temperature in refrigerant circuit

Clean dirty heat exchanger on outdoor
module; rectify possible pneumatic short
circuit on the outdoor device.

fl ashes 4 time

Overcurrent circuit breaker on condenser
(overload) has tripped, or no operating
voltage on condenser

Open any closed spherical valves; check
supply voltage; exchange faulty PCBs

fl ashes 5 time

Fault in hot gas temperature sensor or fi n
temperature sensor (cable breakage or
short circuit)

Check PCB connector for fi rm connection,
check functionality of the sensor

fl ashes 6 time

Temperature fault on inverter cooling
block

Rectify obstruction to fl ow in outdoor
module

fl ashes 7 time

Fault in power supply

Check and repair power supply

fl ashes 4 time

fl ashes 1 time

Fault on liquid line sensor (cable breakage
or short circuit)

Check PCB connector for fi rm connection,
check functionality of the sensor

fl ashes 4 time

Temperature of liquid line too high / too
low

Check refrigerant line or lack of refriger-
ant