Fms to dwyer, Fms dwyer temperature/humidity falcon integration, Fms sensor wiring guide – RLE FMS User Manual

Page 16: Temperature setup humidity setup

Advertising
background image

SHEET:

16 OF 16

104 Racquette Drive

Fort Collins, CO 80524

(970) 484-6510 Phone

(970) 484-6650 Fax

www.rletech.com

FMS Sensor Wiring Guide

10061_FMS Rev 2.0 (8/13)

FMS Dwyer Temperature/Humidity Falcon Integration

Temperature Setup

Humidity Setup

1. Wire th e sensor as shown.

5. Ver ify the "Calc" Valu e d isp lays th e corre ct r oom tempera ture .
The tempe rature can also be viewed on the Falcon ma in page.

SETUP

1. Calculate the Dwyer Ou tpu t cu rrent for te mp erature.

TRO UBLESHOO TING

2. Measure th e curr ent flowing into the Falcon Ch- terminal with a
current me ter. Ver ify that it is close to the calcula ted curren t
(+/-1%)

3. If measured current curr ent do es not ma tch calcula ted curren t
then ch eck wi ring.

4. Compare the me asu red cur rent matches the cu rrent re ading in
the Fal con.

5. Check the wir ing if th e Falcon current readin g d oes no t match
the me asu red cu rrent re ading.

6. If th e Falcon current readin g matches the measured current
and the Fa lco n calculated value does not match the room
temperature then the offset and gain values are wr ong.
Double check the Gain and Offset va lues.

7. If th e tempera ture di spla ye d in the Fa lco n is 1 or 2 deg rees
abo ve or belo w th e r oom tempera ture then adju st the offset b y
1 or 2. Do not adj ust the ga in. Onl y tweak th e o ffse t once the
previou s tr oubleshoo tin g steps ha ve bee n p erfo rmed.

8. If th e Falcon still doe s not d isp lay the cor rect te mp erature
contact RL E Techno logies technical suppor t at 970.484.651 0.

9. Use similar tro ubleshoo ting pro ce dure excep t use the
following formula to calculate the humidity mA output.

mA =

Room Humidi ty

100

x 16 + 4

2. Configure the Fa lcon Input cha nnel (temperature) for "Ana log
4-20mA" and en ter the gain and offset valu es. For the -40 -
140F ra nge use G ain 45, Offset -85.

4. Configure the Fa lcon Input Ch annel (humidity) for "Ana log 4-
20mA" and en ter the Gain of 25 and Offset of -25.

4

5

3. For oth er temper atur e ra nges, use the Calculator fu nction on
the web page

3

5

2

Example if Room Te mp is 70F an d you r sensor has a ra nge of -40 - 140

( (

Act ual t emp - Sensor Low

) / (

Sensor High - Sensor Low

)) x 16 + 4

( (70 - -40) / (140 - -40)) x 16 + 4 = 13.77

-40 - 140 Degree F Range

P1

VDC

TB 1

VDC

+ -

EXT ERNAL

24VDC

+ +

Ch1
+ -

Ch2
+ -

Ch3
+ -

Ch4
+ -

TB 2 Inp ut 1-4

Ch5
+ -

Ch6
+ -

Ch7
+ -

TB 3 Inp ut 5-8

Ch8
+ -

EXT ERNAL

GND

- -

TB 4

NC NO C

RELAY 1

NC NO C

RELAY 2

Figure 16.1: Falcon Wiring with the Dwyer

Temperature/Humidity sensor