Afs(wm/dm), Afs-(wm/dm) f200 integration, Fms sensor wiring guide – RLE FMS User Manual

Page 8: Figure 8.1: fms wiring, Fms configuration

Advertising
background image

SHEET:

8 OF 16

104 Racquette Drive

Fort Collins, CO 80524

(970) 484-6510 Phone

(970) 484-6650 Fax

www.rletech.com

FMS Sensor Wiring Guide

10061_FMS Rev 2.0 (8/13)

AFS-(WM/DM) F200 Integration

FMS Configuration

Figure 8.1: FMS Wiring

1 2 3

SW1

SW2

SW3

FMS AFS-xx Input Configuration Interface

1

2

3

4

P1

V DC

TB 1

V DC

+ -

EXT ERNAL

24VDC

+ +

Ch1

+ -

Ch2

+ -

Ch3

+ -

Ch4

+ -

TB 2 Input 1-4

Ch5

+ -

Ch6

+ -

Ch7

+ -

TB 3 Input 5-8

Ch8

+ -

EXT ERNAL

GND

- -

TB 4

NC NO C

RELAY 1

NC NO C

RELAY 2

1. Set Jumper Switches on AFS-XX to appropriate
settings.
Output Selection SW1:

4-20mA Output

Working Range SW2:

0-2000 Ft/Min Range

0-3000 Ft/Min Range

0-4000 Ft/Min Range

Response Time SW3:

Fast

Slow

2. Set FMS Input Channel to an Analog 4-20 mA.

3. For a 0-2000 Ft/Min Range, use a gain of 500 and an
offset of -500.

4. For other settings, use the integrated gain/offset
calculator.