Timer Control Register
0x00

Bits

Type

Default

Description

[15:8]

WO

0x00

Timer preload data in 100 us ticks.

[7:2]

UU

XXXXXX

Reserved

[1]

WO

0

Timer mode:

0 – manual restart;
1 – auto restart.

[0]

WO

0

Manual restart. Writing a 1 restarts the timer if [1] is 0. Bit [0]
of the Interrupt Status register is set to 1 when timer expires.




Watchdog Timer Control Register
0x02

Bits

Type

Default

Description

[15:5]

UU

X

Reserved.

[4]

WO

0

Solid-state relay control signal polarity: 0 – normal (active
when timed out), 1 – inverted (active when not timed out).
(See Note 2).

[3]

WO

0

Watchdog timer software enable: writing a 1 enables, writing a
0 disables the watchdog timer (see Note 3).

[2:0]

WO

000

Timeout interval:

000 – 16 sec;
001 – 8 sec;
010 – 4 sec;
011 – 2 sec;
100 – 1 sec;
101 – 0.5 sec;
110 – 0.25 sec;
111 – 0.125 sec.


Notes:
1.

Reading the Watchdog Timer Control register “tags” the watchdog (restarts the count). The
data returned by read access is undefined.

2.

The meaning of bit [4] corresponds to the case when a shunt in position 2 of jumper J4 is
NOT installed. If the shunt is installed, the meaning of bit [4] is reversed: 0 corresponds to
normal, and 1 – to inverted polarity of the solid-state relay control signal.

3.

The meaning of bit [3] corresponds to the case when a shunt in position 1 of jumper J4 is
NOT installed. If the shunt is installed, the meaning of bit [3] is reversed: 0 enables, and 1
disables the watchdog timer. Thus installing the shunt enables the watchdog timer by default
after the power up.