1 5

r1 =

Input Type and Range Value

0 =

TC

J

From

-100

to

1000

°C

1 =

TC

K

From

-100

to

1370

°C

2 =

TC

T

From

-200

to

400

°C

3 =

TC

E

From

-100

to

800

°C

4 =

TC

N

From

-100

to

1400

°C

5 =

TC

S

From

-50

to

1760

°C

6 =

TC

R

From

-50

to

1760

°C

7 =

TC

B

From

0

to

1820

°C

8 =

TC

L

From

-100

to

900

°C

9 =

TC

U

From

-200

to

600

°C

10 =

TC

G

From

0

to

2300

°C

11 =

TC

D

From

0

to

2300

°C

12 =

TC

C

From

0

to

2300

°C

13 =

TC Plat. II

From

-100

to

1400

°C

14 =

RTD Pt 100 From

-200

to

850

°C

15 =

Linear

From

0

to

60

mV

16 =

Linear

From

12

to

60

mV

17 =

Linear

From

0

to

20

mA

18 =

Linear

From

4

to

20

mA

19 =

Linear

From

0

to

5

V

20 =

Linear

From

1

to

5

V

21 =

Linear

From

0

to

10

V

22 =

Linear

From

2

to

10

V

23 =

TC

J

From

-150

to

1830

°F

24 =

TC

K

From

-150

to

2500

°F

25 =

TC

T

From

-330

to

750

°F

26 =

TC

E

From

-150

to

1470

°F

27 =

TC

N

From

-150

to

2550

°F

28 =

TC

S

From

-60

to

3200

°F

29 =

TC

R

From

-60

to

3200

°F

30 =

TC

B

From

32

to

3300

°F

31 =

TC

L

From

-150

to

1650

°F

32 =

TC

U

From

-330

to

1110

°F

33 =

TC

G

From

0

to

4170

°F

34 =

TC

D

From

0

to

4170

°F

35 =

TC

C

From

0

to

4170

°F

36 =

TC Plat. II

From

-150

to

2550

°F

37 =

RTD Pt100

From

-330

to

1560

°F

r2 = Decimal Point Position
(Available only for linear range r1 = 15 to 22)

_ _ _ _ .

= No decimal

_ _ _ . _

= One decimal place

_ _ . _ _

= Two decimal places

_ . _ _ _

= Three decimal places

r3 = Low Scale Range Value
(Available only for linear range r1 = 15 to 22)
Range: From -1999 to 9999

r4 = High Scale Range Value
(Available only for linear range r1 = 15 to 22)
Range: From -1999 to 9999

r5 = Offset Adjustment
Range: From -500 to 500
Offset value algebraically added to the measured value.

r6 = Time Constant for Filter on Displayed Value
Range: From 0 (filter OFF) to 8 seconds.
(First order filter with selected time constant.)

r7 = Alarm Action on Fault
uP = The alarm assumes an upscale reading.
doun = The alarm assumes a downscale reading.

C1 = Type of Limit Action
Hi. = High limit (for heating process)
Lo. = Low limit (for cooling process)
Hi.Lo = Band limit (for special process)

C2 = Acknowledgment Mode
O = The acknowledgment action is ignored if performed

when setpoint is exceeded.

I =

The acknowledgment action is recognized also
when the setpoint is exceeded. (In this case, the
control output is instantaneously restored when
process variable is within setpoint).