SPECIFICATIONS

Case

RABS Grey dark color (RAL 7043).
Self-extinguishing degree V0
according to UL 94

Front panel

Designed and tested for IP65 and NEMA
4X for indoor location (when panel gasket
is installed). Tests were performed in
accordance with IEC 529, CEI 70-1 and
NEMA 250-1991 STD.

Installation

Panel mounting

Rear Terminal Block

15 screw terminals with safety rear cover

Dimensions Unit with RS-485 communications

DIN 43700 48 x 48 mm x 122 mm
(1.890 x 1.890 in. x 4.803 in).

Dimensions Unit without RS-485 communications

DIN 43700 48 x 48 mm x 105 mm
(1.890 x 1.890 in. x 4.134 in).

Cutout

45 x 45 mm (1.772 x 1.772 in).

Weight

250 g (8.75 oz).

Upper Display 4 digits, 7 segment red LED’s with

decimal point, 7.62 mm high (0.3 in).

Lower Display 2 digits, 7 segment red LED’s with

decimal point, 7.62 mm high (0.3 in).

Indicator

2 red LED annunciators for:
“RESET” Indicates control output status
as follows:
a)

With configuration parameter
C2 = 0
LED ON when Output is OFF
LED OFF when Output is ON

b)

With configuration parameter
C2 = 1
LED flashes when Output is OFF
LED ON when Output is OFF
and acknowledged
LED OFF when Output is ON

“ALM” indicates alarm status as follows:

Flashes when alarm is ON.
ON when alarm has been
acknowledged
OFF when alarm is OFF

RMT

A decimal point on the right side
of the upper display flashes to
indicate the device is controlled
by serial link

Keyboard

Four keys (covered by polyester mem-
brane) labelled RESET, , & FUNC.

Power Supply 100 to 240 Vac 50/60 Hz switching or

24 Vac/Vdc with interruptions less than
100 ms

Power Supply Variation

-15% to 10% (for 100 to 240 Vac)
-10% to 10% (for 24 Vac/Vdc)

Power Consumption 8 VA max
Insulation Resistance Greater than 100 M

Insulation Strength1500 V rms for 1 minute
EC Compatibility

Conforms with 89/336/EEC directives re-
garding electro-magnetic compatibility
Emission Complies with:
Generic emission standard EN50081-2
Immunity Complies with the generic im-
munity standard EN50082-2. Conforms
with 72/23/EEC and 93/68/EEC directives
regarding low voltage. It complies with the
safety requirements for electrical equip-
ment for measurement, control and
laboratory use, Generic Standard
EN61010-1, Installation Category II.

Sampling
Time

250 ms for linear input
500 ms for TC/RTD input