1 8

(Hysteresis)

ON

ALM LED

OFF

Alarm status*

Relay

No alarm status

ACK

(Alarm
threshold)

FLASH

FLASH

Example for P2 = H.A.A.c

ACK = Alarm acknowledgment from "AK" parameter

or serial link.

* Alarm Status:Relay energized (P3 = dir)

Relay de-energized (P3 =rEV)

Example for P2 = H.L.

ACK = Alarm acknowledgment from "AK" parameter

or serial link.

* Alarm Status:Relay energized (P3 = dir)

Relay de-energized (P3 =rEV)

(Hysteresis)

ON

ALM LED

OFF

Alarm status*

Relay

No alarm status

ACK

ACK

(Alarm
threshold)

FLASH

FLASH

P3 = Alarm Action
(Skipped if option not is available or P1 = none)
dir

=

Direct action
(Relay energized in alarm condition)

rEV =

Reverse action
(Relay energized in non-alarm condition)

P4

=

Alarm Standby Function

(Skipped if option is not available or P1= none)
OFF =

Standby function disabled

On =

Standby function enabled

If the alarm is programmed as band or deviation, this
function masks the alarm condition at start up and at a
“Su” setpoint change until the process variable reaches
the alarm threshold, plus or minus hysteresis. This standby
function masks a Process Alarm condition at start up until
the process variable reaches the alarm threshold plus or
minus hysteresis.

PF = Time Constant for Filter on Measured Value for
Alarm Action
(Skipped if option is not available or P1 = none)
Range: From 0 (filter OFF) to 8 seconds
(First order filter with selected time constant.)

n 1 = Safety Lock
0

=

UNLOCKed. The device is always UNLOCKed
and all parameters can be modified.

l

=

LOCKed. The device is always LOCKed and
no parameters can be modified

From 2 to 9999 = This number is a password, to be used

in run time (see “nn”), to LOCK/UNLOCK the
device.