5.3 Configuration

TD-34 can be configured via AT-commands on the service interface, or by a remote modem (if
the TD-34 is set for remote configuration, see SW 4).

5.3.1 DIP-switch settings

DIP-switches are accessable under the lid on top/front of the unit. DIP-switches are
used to configure the unit.

Warning!

Prevent damage to internal electronics from electrostatic discharges (ESD) by
discharging your body to a grounding point (e.g. use of wrist strap), before the
lid on top/front of the unit is removed.

Warning! Do not open connected equipment.

Prevent access to hazardous voltages by disconnecting the unit from AC/DC mains
supply and all other electrical connections.

NOTE! The change of DIP-switch settings are valid only after a power on.

If configured by any other method during normal operation, this new
configuration override the DIP-switch settings. However, after a new
power on the DIP-switch settings have precedence.

!

!