AEC Glacier Series Air and Water Cooler Portable Chillers User Manual

Page 13

Advertising
background image

Page 12

Glacier Series Portable Chillers

Figure 1

Glacier NXGA Air-Cooled Chiller Capacities and Specifications

Air in

10-30 hp

Air

out

5-30 hp

Air in

Controller with
graphic panel

Electrical

enclosure

B

A

Allow 6" to 8" for piping

Sight glass

From Process

3/4" drain plug

To Process

2.5"-dia. To Process

pressure gauge

1"

F

System fill

C

D

E

Glacier Series NXGA Air-Cooled Model Capacities

• Nominal operating parameters for Glacier Series NXGA air-cooled models are 50ºF

leaving water temperature at 2.4 gpm per ton with 95ºF ambient air.

Nominal cooling capacity

c Water

Com-

Nom.

Power in amps

f, 460/3/60 g

Model tons flow

pressor pump

Discharge

air

e

1 pump

2 pumps

number no pump 1 pump 2 pump gpm

d

hp hp openings

cfm

rated

running

rated running

NXGA5 5.03 4.73 4.63

11.4 5 1.5 1 @ 27”

6,000 13.79 12.42 14.69

13.32

NXGA7.5 7.69 7.39 7.29 17.7

7.5 1.5

1 @ 27”

6,000 20.53 17.68 22.33

21.43

NXGA10 9.91 9.61 9.51 23.1 10 1.5 2 @ 27”

12,000 27.93 23.13 29.73

28.83

NXGA15 15.23 14.93 14.83 35.8 15

1.5

2 @ 27”

12,000 35.83 31.13 38.43

37.13

NXGA20 17.07 16.47 16.27 39.5 20

3.0 2,

@17.5”x19” 18,000 51.54 44.09 52.99

45.54

NXGA25 21.52 20.92 20.72 50.2 25

3.0 2,

@17.5”x19” 18,000 59.64 51.69 62.25

54.30

NXGA30 25.11 24.11 23.71 57.9 30

5.0 2,

@17.5”x19” 18,000 67.24 60.84 69.85

63.45

c Based on 50ºF chilled water supply temperature and 95ºF ambient air. Optional additional process pump hp reduces

chiller capacity by 0.2 tons per hp.

d Based on 2.4 gpm per ton, nominal 1 pump. Optional additional process pump hp reduces chiller capacity by 0.2 tons

per hp.

e Customer use of ductwork requires optional high-pressure fan for 5 hp to 15 hp models.
f An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total chiller

amperage, subtract the standard process pump amperage from the optional pump amperage (see bottom of Page 4),
and add it to the chiller rated or running amperage.

g Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 0.8 for 575/3/60 amperages.

Glacier Series NXGA Model Specifications

• NXGA portable chillers come standard with 4” swivel casters.

Com-

Process connections, in. NPT Dimensions

Shipping Operating

Model

pressor

1

2

no pump,

1 pump, no in

inches weight

weight

number

hp

pump pumps no tank tank, to/from

A

B

C

D

E

F

lbs.

lbs.

NXGA5

5

1.5

2.0

1.5

1.5 / 2.0 65

34

77.5 31.75 9.5

17 1,309 1,502

NXGA7.5 7.5

1.5 2.0 1.5

1.5

/

2.0 65

34

77.5 31.75 9.5

17 1,377 1,570

NXGA10

10

1.5

2.0

1.5

1.5 / 2.0 65

34

77.5 31.75 9.5

17 1,530 1,723

NXGA15

15

2.0

2.5

2.0

2.0 / 3.0 65

34

77.5 32.88 9.5

17 2,108 2,205

NXGA20

20

2.0

2.5

2.0

2.0 / 3.0 78

34

87.5 32.88 9.5

17 2,477 2,671

NXGA25

25

2.0

2.5

2.0

2.0 / 3.0 78

34

87.5 32.88 9.5

17 2,493 2,687

NXGA30

30

2.5

3.0

2.5

2.5 / 3.0 78

34

87.5 34.50 9.5

17 2,782 3,022

Advertising