4 freezestat light, 5 low oil pressure light, 6 power light – AEC Glacier Series Air and Water Cooler Portable Chillers User Manual

Page 56: 7 hot-gas bypass light, 8 compressor light

Advertising
background image

Glacier Series Portable Chillers

Page 55

7-4 Freezestat Light

This indicator lights if the chilled water temperature drops below the Freezestat setting. This
prevents possible system freeze-up. The compressor will shut off and the chilled water pump will
continue to operate.

Caution!

Your AEC, Inc. warranty does not cover damage from system freeze-up.

Make sure the freezestat is set properly to prevent freeze-up!


7-5 Low Oil Pressure Light

This indicator light, installed on chillers with 15 horsepower compressors and larger, lights if
compressor oil pressure drops to a dangerous level. After two minutes of low oil pressure, the
compressor will shut down.

This is a manual reset control. Call a qualified refrigeration service technician or the Application
Engineering Service Department for repairs.

7-6 Power

Light

This indicator lights whenever the power switch is in the ON position and the control circuit is
energized.

Note: The crankcase heater is energized whenever main power is applied to the chiller. The

position of the power switch does not affect the operation of the crankcase heater.


7-7 Hot-Gas Bypass Light

This indicator lights when the hot-gas bypass valve is in operation. The "OUT" LED on the NX
Controller will also light when the hot-gas bypass valve is in operation.

7-8 Compressor

Light

This indicator lights whenever the compressor is operating.

Advertising