AEC Glacier Series Air and Water Cooler Portable Chillers User Manual

Page 17

Advertising
background image

Page 16

Glacier Series Portable Chillers

Figure 5

NXGW Series Water-Cooled Chiller Design Specifications

Condenser

q

Model

Number

Cooling

Capacity

Chilled

Water

Standard

Pump

Pipe
Size

Total

Running

Amps p

City

Water

Tower

Approximate

Dimensions

L X W X H

Approx.

Shipping

Weight

Tons

n

gpm

o

Hp

Inches

GPM

GPM

Inches

(Lbs)

NXGW5

6

12

2

27

6

18

65 X 34 X 45

1,400

NXGW7.5

8

18

2

35

10

24

65 X 34 X 45

1,600

NXGW10

10

24

2

47

12

31

65 X 34 X 45

1,625

NXGW15

15

36

2

65

18

45

65 X 34 X 45

1,900

NXGW20

19

45

3

2

79

25

60

78 X 34 X 45

2,100

NXGW25

24

60

3

2

95

30

75

78 X 34 X 45

2,200

NXGW30

27

72

5

2

131

36

90

78 X 34 X 45

2,200

n Based on 50°F chilled water supply temperature. Consult factory for other requirements.
o Flow rate based on 2.4 gpm/ton. Alternate pump selections available.
p 208-230/3/60
q Requirement based on availability of 70°F city water or 85°F tower water at 25 psi minimum. Consult factory for other
conditions.

Table 2

NXGA Series Air-Cooled Chiller Design Specifications

Model

Number

Cooling

Capacity

Chilled

Water

Standard

Pump

Pipe Size

Total

Running

Amps p

Condenser

Air Flow

Approximate

Dimensions

L X W X H

Approx.

Shipping

Weight

Tons

n

GPMo Hp Inches

CFM

Inches

(Lbs)

NXGA5

5

12

2

30

6,000

65 X 34 X 77

1,300

NXGA7.5

7

18

2

39

6,000

65 X 34 X 77

2,100

NXGA10

24

2

54

12,000

65 X 34 X 77

2,300

NXGA15

13½

36

2

72

12,000

65 X 34 X 77

2,400

NXGA20

17½

45

3

2

105

18,000

78 X 34 X 87

2,450

NXGA25

23

60

3

2

121

18,000

78 X 34 X 87

2,600

n Based on 50°F chilled water supply temperature and 95°F ambient air temperature. Consult factory for other requirements.
o Flow rate based on 2.4 gpm/ton. Alternate pump sizes available.
p 208 - 230/3/60

Advertising