Configuration guidelines, Miranda imaging frames (symphonie or quartet 2), Miranda densité frames – Grass Valley iControl Solo v.4.13 User Manual

Page 10

Advertising
background image

Installation and Network Requirements

Configuration Guidelines

6

Configuration Guidelines

Miranda Imaging Frames (Symphonie or Quartet 2)

• iControl Solo supports a maximum of 100 Miranda interface cards (Densité and Imaging

combined).

• Quartet 1 and Solo frames are not supported.

• A maximum of four frames can be connected to each RS-422 communication port.

• When critical on-air equipment is controlled (e.g. incoming feeds) do not connect more

than two frames per RS-422 communication port.

• When using Symphonie frames that are fully loaded with XVP-801/811 and/or DAP-781

cards, do not connect more than one frame per RS-422 communication port.

Miranda Densité Frames

• iControl Solo supports a maximum of 100 Miranda interface cards (Densité and Imaging

combined).

• Thumbnail, audio level, closed captioning, and other similar probing features are not

supported in iControl Solo.

• Each frame must be registered to a single iControl Solo application. Ensure that the frame

is not registered to an iControl Application Server RCP-100 or RCP-200 device. Having the
same frame report to multiple Densité Managers may result in repeated loss of connection
and system instability. The Densité Controller only supports one client connection at a
time.