0 storage, 0 installation – Energy Tech Laboratories EDP70 User Manual

Page 13

Advertising
background image

MI00/10056 rev.1--05/2001-- page

13

3.0

STORAGE

If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral
battery becoming discharged thereby sustaining permanent damage and affecting the standby period available
and battery life. The date the battery was last recharged and the date the battery is due for its next recharge are
both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge
date.
When the EDP70 PLUS is due to be recharged, refer to the Installation instructions and connect the EDP70 PLUS
UPS to a temporary AC supply. The battery MUST be recharged for at least 24 hours every 3 months.

4.0

INSTALLATION

4.1

Mechanical characteristics

-

Ambient temperature

18

°

F[-10

°

C] to 104

°

F [+40

°

C ]

-

Relative Humidity (w/out condensing @ 68

°

F[20

°

C])

< 90%

-

Max altitude (w/out derating)

3300 feet [1000 m] above sea-level

-

Protection degree (panel fitted)

-

Input cables

bottom

-

Air inlet

bottom

-

Air outlet

rear

UPS model

Description

u.m.

24

36

50

80

Size

width

depth

height

In

[mm]

27.5 [700]
28.7 [730]

56 [1420]

27.5 [700]
28.7 [730]

56 [1420]

35.4 [900]
28.7 [730]

63 [1600]

35.4 [900]
28.7 [730]

63 [1600]

Total

Weight

(UPS +

Battery)

w/out cells

25 Ah cells
30 Ah cells
35 Ah cells

Lbs
[kg]

880 [400]

1342 [610]
1456 [662]
1526 [694]

1300 [590]

n.a.
n.a.
n.a.

1342 [610]

n.a.
n.a.
n.a.

1800 [818]

n.a.
n.a.
n.a.

Floor Area

In

2

[m

2

]

789 [0.511]

789 [0.511]

1019 [0.657]

1019 [0.657]

Floor

Loading

(UPS +

Battery)

w/out cells

25 Ah cells
30 Ah cells
35 Ah cells

Lbs/in

2

[kg/m

2

]

1.12 [782]

1.70 [1194]
1.85 [1296]
1.93 [1358]

1.65 [1155]

n.a.
n.a.
n.a.

1.32 [930]

n.a.
n.a.
n.a.

1.77 [1245]

n.a.
n.a.
n.a.

Air-Flow

cfm

[mc/h]

235

[400]

647

[1100]

Acoustic Noise

100% Linear Load

dBA

52

55

Notes:

1)

n.a. = not applicable

2)

Longer autonomies, and battery for EDP above 20 kVA are available with external
battery cubicles.

Advertising