0 connection, Figure 15 – connection diagrams – Energy Tech Laboratories EDP70 User Manual

Page 25

Advertising
background image

MI00/10056 rev.1--05/2001-- page

25

5.0

CONNECTION

Figure 15 – Connection diagrams

THE AC AND DC SUPPLIES TO THE EDP70 PLUS UPS, AND THE AC OUTPUT FROM THE UPS, SHOULD BE FED
THROUGH SUITABLY RATED CIRCUIT BREAKER OR FUSE(S) AND ISOLATING SWITCH SUITABLE FOR BRANCH
CIRCUIT PROTECTION.
NOTE:

INTERRUPTING THE NEUTRAL FEED MAY CAUSE THE CHANGE IN GROUND-NEUTRAL VOLTAGE TO
AFFECT THE LOAD.

NOTE:

ALL CIRCUIT BREAKERS OR FUSES AND ISOLATING SWITCHES SHOULD BE FITTED AS CLOSE TO THE
EDP70 PLUS UPS AS POSSIBLE AND MARKED WITH THE LABELS PROVIDED WITH THE UNIT.
IT IS ALSO RECOMMENDED A LABEL AS FOLLOWS

Protection devices to be installed by the customer

EXTERNAL
BATTERIES

Protection devices to be installed by the customer
according to the information shown on page 23

according to the information shown on page 23

OUTPUT

OUTPUT

EXTERNAL
BATTERIES

Remove link to connect remote E.P.O.

Remove link to connect remote E.P.O.

Neutral not
present on
50 and 80kVA
ratings

(Neutral separately derived
on 50 and 80kVA ratings)

(Neutral separately derived
on 50 and 80kVA ratings)

UTILITY
INPUT

INPUT

RESERVE

L1
L2
L3

L1
L2
L3
N

UTILITY
INPUT

L1
L2
L3
N

6

GROUND

Neutral not
present on
50 and 80kVA
ratings

A
B
C

G

A
B
C
N

1
2
3
4
5

A
B
C
N

Thermostick contacts

Battery Charge Inhibit

L1
L2
L3
N

GROUND

G

1
2
3
4
5
6

A

N

C

B

N

A
B
C

Thermostick contacts

Battery Charge Inhibit

N

L1
L2
L3